Publication 2093-UM001A-EN-P — March 2007

Specifications and Dimensions

157

Shunt Module Power Specifications

The table below lists the power specifications for the 2093-ASP06
Shunt Module (SM).

SM Power Specifications

Circuit Breaker/Fuse Specifications

While circuit breakers offer some convenience, there are limitations for their
use. Circuit breakers do not handle high current inrush as well as fuses. A
Kinetix 2000 system needs to be protected by a device having a short circuit
interrupt current rating of the service capacity provided or a maximum of
100,000 A.

If an upstream circuit protection device is rated for the overload current and
short circuit rating, a supplementary circuit protection device (such as the 1492
product) can be used as the only Kinetix 2000 branch-circuit protection
device. The upstream fully rated device let-through must be less than or equal
to the 10 kA interrupt rating of the 1492 circuit protection device.

The wiring interconnection in the figures below provide examples of the
needed protection and follows UL and NEC codes. Full compliance is
dependent on final wiring design and installation.

Circuit Protection under NEC 1999 110-10 (preferred fully rated devices)

Kinetix 2000 Drives

Shunt Module
Catalog Number

Specifications

Fuse
Replacement

Drive
Voltage
V ac

Resistance

Ω

Peak
Power
kW

Peak
Current
A

Continuous
Power
W

Capacitance

μF

2093-AC05-MP1

2093-ASP06

(1)

230 15.0 10.9 27.0 50

164

N/A (no internal
fuse)

2093-AC05-MP2

2093-AC05-MP5

(1)

1Contact your Allen-Bradley sales representative for availability of external shunt modules.

Required Protection

under 110-10 of

NEC 1999

Preferred Fully

Rated Breakers

Distribution
Blocks

Fully Rated

Fused

Disconnect
Fully Rated

Breaker

Drive

Drive

Drive

Fully Rated

Fused

Disconnect
Fully Rated

Breaker

Breakers Selected

for Device Protection

Fully Rated Short Circuit

Interrupt Capability

Required Protection

under 110-10 of

NEC 1999

Preferred Fully

Rated Breakers

Fully Rated
Fused
Disconnect
Fully Rated
Breaker

Breakers Selected

for Device Protection

Fully Rated Short Circuit

Interrupt Capability