If this product is installed within the European Union or EEC regions and has
the CE mark, the following regulations apply.

For more information on electrical noise reduction, refer to the System Design
for Control of Electrical Noise Reference Manual, publication GMC-RM001.

CE Requirements (System without LIM)

To meet CE requirements when your Kinetix 2000 system does not include
the line interface module (LIM), the following requirements apply.

• Install an ac line filter (2090-XXLF-xxxx) as close to the integrated axis

module (IAM) as possible.

• Use 2090-series motor power cables or use connector kits.
• Combined motor power cable length for all axes on the same dc bus

must not exceed 160 m (525 ft) with 230V systems. Drive-to-motor
power cables must not exceed 30 m (98.5 ft).

• Use 2090-series motor feedback cables or use connector kits and

properly terminate the feedback cable shield. Drive-to-motor feedback
cables must not exceed 30 m (98.5 ft).

• Install the Kinetix 2000 system inside an enclosure. Run input power

wiring in conduit (grounded to the enclosure) outside of the enclosure.
Separate signal and power cables.

Wiring instructions are available in Chapter 5 of this publication. Product
catalog numbers are listed in the Kinetix Motion Control Selection Guide,
publication GMC-SG001.

ATTENTION

Meeting CE requires a grounded system, and the method of grounding
the ac line filter and drive must match. Failure to do this renders the
filter ineffective and may cause damage to the filter.

For grounding examples, refer to Determining Your Type of Input
Power on page 63.