Calculating Total Bus
Capacitance

Total bus capacitance is the sum of all capacitance values for your Kinetix 2000
common bus modules. Specifically, this includes the capacitance values for
each of these modules.

• Leader IAM (converter and inverter)
• Each AM and SM (if present) on the leader IAM power rail
• Each follower IAM (converter and inverter)
• Each AM on the follower IAM power rails

Refer to Kinetix 2000 Capacitance Values on page 211 for IAM/AM/SM
capacitance values.

Calculating Additional Bus
Capacitance

Additional bus capacitance is the sum of all follower IAM and AM capacitance
values for your Kinetix 2000 common bus modules. Specifically, this includes
the capacitance values for each of these modules:

• Each follower IAM (converter and inverter)
• Each AM on the follower IAM power rails

Enter the additional bus capacitance values in step 6 of Setting the Additional
Bus Capacitance Parameter.

IMPORTANT

If total bus capacitance exceeds the leader IAM maximum value, a
pre-charge time-out fault is triggered, and error code E90 is displayed.

This fault disables the drive.

If the Leader IAM (230V) is

the Total Bus Capacitance must not exceed

2093-AC05-MP1

3420 µF

2093-AC05-MP2

2093-AC05-MP5

IMPORTANT

If your total bus capacitance value exceeds the value in the table
above, you must decrease the total bus capacitance by removing axis
modules.