Planning the Kinetix 2000 Drive System Installation

Minimum Clearance Requirements

This section provides information to assist you in sizing your cabinet and
positioning your Kinetix 2000 system components.

Minimum Clearance Requirements

(1)

The power rail, catalog number 2093-PRSxx, does not extend left of the first module or right of the last module.

Minimum Clearance Dimensions

IMPORTANT

Mount the module in an upright position. Do not mount the module on
its side.

Clearance right of the
module is not required.

(1)

Clearance above

for airflow and installation.

Clearance left of the

module is not required.

(1)

Integrated Axis Module (IAM),
catalog number 2093-AC05-MP1,
is shown mounted on power rail
as the first module.

Clearance below

for airflow and installation.

Cat. No.

Clearance Above, Min

Clearance Below, Min Cabinet Depth Clearance, Min

(1)

2093-AC05-MP1,
2093-AC05-MP2,
2093-AC05-MP5.
2093-AMP1,
2093-AMP2,
2093-AMP5,
2093-AM01,
2093-AM02

50.8 mm (2.0 in.)

50.8 mm (2.0 in.)

200 mm (7.9 in.)

If 15-pin connector kit, catalog number
2090-K2CK-D15M, is attached.

235 mm (9.25 in.)

44-pin connector kit options include:

• 2090-U3BK-D44xx connector kit

(containing a 2090-U3BK-D44 terminal
block and 2090-U3BK-D44xx cable)

• 2090-U3BK-D44 terminal block and

custom-built cable.

• 2090-U3BK-D44 terminal block and flying

lead cable.

2093-ASP06

305 mm (12.0 in.)

50.8 mm (2.0 in.)

200 mm (7.9 in.)

2093-PRF

None None None

(1)

Additional clearance required to accommodate cable bend restrictions.