Kinetix 2000 Connector Data

Contactor Enable Relay Circuit

Contactor Enable Relay Output Specifications

Motor Brake Relay

Two connections are required for the (customer-supplied) motor brake input
power (BC-1 and BC-2) and two connections each for the motor brake output,
as shown in the figure below. Connections are rated for +24V and current as
shown in the table below.

An active signal releases the motor brake (BC-2 and BC-3). The brake signal
on each inverter contains a suppression device. The brake turn-on delay
specified in RSLogix 5000 software delays application of the motor brake
activation by the time interval specified, and the brake turn-off delays release
of the motor brake by the time interval specified for the signal.

Refer to Axis Module/Motor Wiring Examples beginning on page 178 and
Controlling a Brake Example on page 181 for wiring examples.

IMPORTANT

All power rail slots must have the proper module installed or the
Contactor Enable relay will not close.

ATTENTION

To avoid damage to the drive, wire the Contactor Enable relay in your
safety control string so that three-phase power is removed from the
drive in the event of certain fault conditions.

Refer to Power Wiring Examples on page 169 for wiring examples.

CONT EN-

CONT EN+

Normally

Open

Relay

Kinetix 2000 IAM

Parameter

Description

Min

Max

On-state
current

Current flow when the relay is closed

1 A

On-state
resistance

Contact resistance when the relay is closed

1

Ω

Off-state
voltage

Voltage across the contacts when the relay is open

120V ac or
24V dc