Harrington Signal IS815 User Manual

Harrington Signal Sensors

Advertising
background image

© Apollo Fire Detector Ltd 2004

Harrington Signal Inc., 2519 4th Avenue, Moline, Illinois 61265, USA

Tel: 800 577 5758

Fax: 309 762 8215

Website: www.harringtonfi re.com

4

1

I-Spy Mini Switch Monitor Module and

I-Spy Mini Priority Switch Monitor Module

Installation Instructions

General
The I-Spy Mini Switch Monitor Module, part no IS816, is a loop-powered device, which
incorporates a monitored input circuit for connection to switches. The module is supplied as
a small plastic housing designed to fit into an electrical box. Six flying leads of 18AWG are
used to connect the module.

A red LED flashes in synchronization with the current pulse reply from the device. If output
bit 2 is set the LED is illuminated continuously.

The I-Spy Mini Priority Switch Monitor Module, part no IS815, has, in additon, a priority
interrupt facility to give fast response and can be fitted in an electrical box behind a pull
station.

Note: the I-Spy Mini Switch Monitor Module and the Mini Priority Switch Monitor Module are
not designed for outdoor use unless they are mounted in a suitable weatherproof enclosure.

Installation
1. The I-Spy Mini Switch Monitor Module and the I-Spy Mini Priority Switch Monitor Module

are not physically attached to the electrical box other than by means of the flying leads.

2. Connect the modules for Class A wiring or Class B wiring (Fig 2). Bit 8 of the DIL

switch is used to select the class of wiring. All wiring must conform to local codes and
regulations.

39214-239/Issue 2

Functional Test Data

OUTPUT

BIT

FUNCTION

INPUT

BIT

FUNCTION

2

ALARM

LED

2

ALARM

LED

CONFIRMATION

1

=

ON

1

=

ON

0

=

OFF

0

=

OFF

1

REMOTE

TEST

1

INDICATES

WIRING

CLASS

1

=

TEST

ENABLED

1

=

CLASS

B

*

0

=

NORMAL

0

=

CLASS

A

0

NOT

USED

0

ALARM

STATUS

1

=

ALARM

0

=

NORMAL

* Note: Toggles to ‘0’ in alarm.

Technical Data
Monitored

circuit

Current

consumption

Quiescent 600µA

Alarm

(LED

on)

4.6mA


End-of-line supervisory resistance

47kΩ, 0.5W

Analog

levels

Open-circuit

fault

4

Normal

16

Alarm on switch closure

64

Compatibility Information
The I-Spy Mini Switch Monitor and I-Spy Mini Priority Switch Monitor modules have been
approved by Underwriters Laboratories Inc. for use with the Fire Spy

Tracker 8000 control

panel.

Advertising