tekmar 741 Actuating Motor User Manual

Installation & operation manual, 741_d, Actuating motor 741

Advertising
background image

Actuating Motor 741

741_D

03/14

Accessories

Replaces: 12/08

Installation & Operation Manual

1 of 2

© 2014 741_D - 03/14

The Actuating Motor 741 is designed to operate any of the tekmar 3-way and 4-way brass mixing valves from type 710
through to type 724. The 741 provides 6 N•m (53 in•lbs) of torque over a 90° rotation. The actuating motor rotates its output
shaft whenever 24 V (ac) is applied between either the counter clockwise (

) or clockwise (

) terminals and the Com

terminal. The motor is compatible with any control having a 24 V (ac) floating output.

Installation

STEP ONE --------------

-------------- GETTING READY ----------------------------------------------------------------------------------------------------

----------------------------------------------------------------------------------------------------

Check the contents of the package. If any of the items listed below are missing or damaged, please refer to the Limited Warranty
and Product Return Procedure on the back of this brochure and contact your wholesaler or local tekmar representative.

Type 741 includes:

• One Actuating Motor 741, One coupler with white arrow, One coupler with red arrow, One

hand wheel with red indicator stripe, Two anti-rotation bolts & One Manual 741_D.

Actuating
Motor

Hand Wheel

Coupler

Anti-Rotation
Bolts

Valve

STEP TWO -------------

------------- MOUNTING -----------------------------------------------------------

-----------------------------------------------------------

• Remove the manual valve handle from the mixing valve.

• Thread the two anti-rotation bolts to the two top holes on the valve body.

• Use the following chart to select the proper coupler:

Type

Coupler Arrow Color

710, 711, 712, 713, 714

White

720, 721, 722, 723, 724

Red

• The arrow on the coupler points towards the valve body. Place the coupler onto the

valve shaft.

• Set the actuating motor’s automatic / manual selector to the manual setting.

• Place the actuating motor onto the coupler. Ensure that the actuating motor’s rotation

range matches that of the mixing valve. Manually rotate the valve using the actuator
hand wheel.

• Ensure the actuating motor’s hand wheel position indicator (clear plastic film with

red stripe) indicates the proper direction to open the valve. If required, the clear
position indicator can be reversed.

• Remove the hand wheel and fasten the actuating motor to the mixing valve using

the screw under the hand wheel. Replace the hand wheel when finished.

• Set the actuating motor’s automatic / manual selector to the automatic setting.

STEP THREE

----------

---------- WIRING ----------------------------------------------------------------

----------------------------------------------------------------

• Use a Phillips screwdriver to remove the two screws on the top of the actuating motor to remove the wiring cover.

• All electric wiring enters the actuating motor through the 1/2" (12 mm) conduit hole on the bottom. Standard 18 AWG solid

wire is recommended for all connections to the motor terminals.

Actuating Motor 741

C

1

2

3

Mixing Control

Powered Output

R

R

C Opn Cls

Clockwise

to Open

C

C

R

R

C

1

2

3

Mixing Control

Unpowered Output

R Opn Cls

Mix

Actuating Motor 741

Class 2

Transformer

24 V (ac)

Clockwise

to Open

The actuating motor is not suitable for use with rigid conduit.

• The diagram below shows wiring for clockwise to open. Reverse the Open and Close wires for counter clockwise to open.

• Use the Test button on the mixing control to verify that the mixing valve fully opens and closes.

• The protection provided by the equipment may be impaired if not installed in a manner specified by these instructions.