Table 1.1: Summary of PPs Flex Venting Options

VENT OPTION #

9

10

CLASSIFICATION USED IN THIS MANUAL

PPs FLEX

(MASONRY)

PPs FLEX

(MASONRY)

ILLUSTRATED IN FIGURE

1.0

1.0

VENT PIPE PENETRATION THROUGH STRUCTURE

CHIMNEY CAP

CHIMNEY CAP

AIR INTAKE PENETRATION THROUGH STRUCTURE

CHIMNEY CAP

CHIMNEY CAP

MIN CHASE ID (ROUND)

6” DIA

7” DIA

MIN CHASE ID (RECTANGULAR)

6” x 6”

7” x 7”

NOMINAL PPs FLEX LINER SIZE

80 mm

100mm

CONCENTRIC VENT/INTAKE CONNECTOR SIZE

80/125

100/150

MAXIMUM

T

O

T

A

L

VENT

LENGTH

(INLUDING PPS FLEX IN CHASE)

VENT

BWC070

51ft

BWC090

51ft

BWC120

51ft

BWC151

51ft

BWC150

47ft

BWC225

45ft

BWC300

68ft

INLET

BWC070

51ft

BWC090

51ft

BWC120

51ft

BWC151

51ft

BWC150

47ft

BWC225

45ft

BWC300

68ft

MAX CHASE HEIGHT

32ft

32ft

CROWN PPs FLEX LINER PART # (32ft COIL)

230955

230956

CROWN PPs FLEX INSTALLATION KIT PART #

230958

230959

Advertising