General 2.1, To and from process connections 2.2 – Conair VL Series User Manual

Page 10

Advertising
background image

2.1

GENERAL

A.

All process piping materials (such as hose, rigid piping, valves or
filters) used in process water piping circuitry must be rated for
100°F minimum temperature and 100 PSI minimum pressure.

B.

All such materials must have the equivalent or larger diameter of
the particular process connection that length of process water
piping is connected to.

Page: 10

VL Series Portable Chillers, 0.25 to 1.5 Tons

UGH020/0301

2.2

TO AND FROM PROCESS CONNECTIONS

A.

Connect the chiller’s “to process” connection to the “water in”
manifold on the mold or process.

B.

Connect the chiller’s “from process” connection the “water out”
manifold at the mold or process.

C.

Process water piping circuitry should be designed to avoid an
excessive use of elbows and/or lengths of pipe or hose. If hose is
the material of choice, avoid tight twists or curls and excessive
lengths.

D.

Valves and filters may be installed in the process water piping
circuitry to facilitate service and maintenance provided that such
devices maintain the full inside diameter of the process connection.
If installed, all such devices must be open and clean during unit
operation.

To process connection:

connect to “water in” on process manifold

From process connection:

connect to “water out” on process manifold

Advertising