Chiller capacity and derate chart 8.5 – Conair VL Series User Manual

Page 39

Advertising
background image

Page: 39

UGH020/0301

VL Series Portable Chillers, 0.25 to 1.5 Tons

8.5

CHILLER CAPACITY AND DERATE CHART

60

50

45

40

35

30

25

20

15

10

5

0

-5

*

*

*

*

*

105%

100%

90%

80%

70%

60%

50%

40%

30%

22%

15%

9%

5%

OUTPUT

TEMPERATURE

°F

FULL
AVAILABLE %
CAPACITY

NOTES:

If operation of the chiller at less than 48°F is
required, an inhibited propylene glycol
solution is required.

Consult factory for chiller operation below
20°F.

Ambient conditions affect air cooled chiller
operation and capacity. Standard rating is at
95°F entering air temperature. For ambient
air conditions greater than 95°F, chiller
derating will occur. For ambient temperatures
of 95-105°F, select the next larger capacity
chiller. For ambient temperatures over 105°F,
consult factory.

* These ranges require special options.

Standard chiller rating is at 50°F. For all other temperature settings,

output tonnage is altered as follows: