Cabling Instructions for the –48 VDC Power Supply
Assembling and Connecting the Safety Ground Wire
1 Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm
(0.175 inches) of copper wire.
2 Using a hand-crimping tool, crimp the ring-tongue terminal to the green/yellow wire.
3 Connect the safety ground to the grounding post on the back of the system using a #8-32 nut
equipped with a locking washer (see Figure 1-2).
Figure 1-2.
Power Supply Safety Ground
Connecting the –48 VDC Power Cable
To connect the
–48 VDC
power cable, plug the
–48 VDC
power cable into the system power supply.
1
green/yellow safety ground
2
grounding post
3
locking washer
4
#8-32 nut
1
2
3
4