Verifying power supply operation – Cisco ASR 1004 User Manual

Page 20

Advertising
background image

20

Step 8

Connect the other ends of the terminal block cables to the site ground connection. Move the circuit-breaker switch to
the On position (|).

This completes the procedure for connecting DC-input power. Your installation is complete. Proceed to the

“Start the System”

section on page 14

to start the router.

Note

After powering off the router, wait a minimum of 30 seconds before powering it on again.

Verifying Power Supply Operation

Follow this procedure to verify power supply is operating correctly.

Step 1

Check that the power supply LEDs are:

INPUT OK is green

FAN OK is green

OUTPUT FAILED is not illuminated

Step 2

To ensure that the power supply state is OK, type the show platform command. This output sample is from a Cisco
ASR1004 router. The other Cisco ASR1000 routers display similar type of output.

MCP_SCAL_R1#sho plat

Chassis type: ASR1004

The following output displays:

MCP_SCAL_R1#

If the LEDs indicate a power problem or the power supply state is ps,fail, then contact a customer service representatives for
assistance or additional instructions.

Slot

Type

State

Insert Time

1

ASR1000-SIP10 ok

00:03:19

1/1

SPA-8X1GE-V2

ok

00:02:23

2

ASR1000-SIP10

ok

00:03:19

2/0

SPA-1X10GE-L-V2

ok

00:02:22

2/1

SPA-8X1GE-V2 ok

00:02:17

R0

ASR1000-RP1

ok,active

00:03:19

F0

ASR1000-ESP20

ok,active

00:03:19

P0

ASR1004-PWR-AC

ok

00:02:50

P1

ASR1004-PWR-AC

ps, fail

00:02:50

Slot

CPLD Version

Firmware

Version

1

07091401

12.2(33r)XN2

2

07091401

12.2(33r)XN2

R0

08060301

12.2(0:0)

F0

08041102

12.2(33r)XN2