Installation – Craftsman 351.223140 User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

ATTACH INLET

Refer to Figure 7.

Inlet needs to be attached to right side of dust collector
assembly. To attach inlet:

Position inlet over 2'h" hole on right side of dust collector
assembly.

Secure inlet using four 4.2-1.4 x 12mm thread-forming
screws.

ATTACH HOSE

Refer to Figure 8.

Hose needs to be attached to the inlet using hose clamp.

To attach hose:

Slide hose clamp onto one end of hose. Loosen clamp
screw if required to slide hose clamp onto hose.

Position the hose clamp wires on the hose grooves.

Slide hose with clamp onto inlet.

Tighten hose clamp screw to secure hose with inlet.

Slide other hose clamp onto the opposite hose end. This
end will be connected to the dust producing machine

Ill®

-os:

. Jl,

Hose

^^^^^■ClampJ

Figure 8 - Attaching Hose

INSTALLATION

DANGER;

Do not permit fingers to touch terminals of plug

when installing or removing the plug to or from the outlet.

WARNING:

Do not connect to power source until unit is

completely assembled.

POWER SOURCE

Motor is designed for operation on the voltage and fre­
quency specified on motor nameplate.

Normal loads will be handled safely on voltages not more
than 10% above or below the specified voltage.

Running unit on voltages not within range may cause over­

heating and motor burnout.

GROUNDING INSTRUCTIONS

Refer to Figure 9.

This tool is equipped with a 3-conductor cord.

Do not remove or alter grounding prong in any manner. In
the event of malfunction or breakdown, grounding provides
path of least resistance for electrical current to reduce risk
of electrical shock.

Plug must be plugged into a matching outlet that is proper­
ly installed and grounded in accordance with all local
codes and ordinances.

The conductor with insulation having an outer surface
which is green is equipment grounding conductor. If repair
or replacement is necessary, make sure equipment
grounding conductor is not connected to line terminal.

If power cord is worn, cut or damaged in any way, have it

replaced immediately.

Properly Grounded Outlet

Grounding Prong

3-Prong Plug

Figure 9 - 3-Prong Receptacle

CAUTION: Improper connection of the equipment-grounding

conductor can result in a risk of electrical shock.

EXTENSION CORDS

The use of any extension cord will cause some drop in the
voltage and loss of power.

Wires of the extension cord must be sufficient in size to
carry the current and maintain adequate voltage.

Use the table below to determine the minimum wire size
(A.W.G.) extension cord.

Use only 3-wire extension cords having 3-prong grounding
type plugs and 3-pole receptacles which accept the tool
plug.

If extension cord is worn, cut or damaged in any way, have

it replaced immediately.

Extension Cord Length

Wire Size

A.W.G.

Up to 50 ft........................................................................................ 16

Note; Using extension cords over 50 ft. long is not
recommended.

Advertising