Just Better SH-35N Superheat Subcooling User Manual

Sh-35n, And sh-36n

Advertising
background image

Not intended for use on hazardous or corrosive fluids

GAUGE SPECIFICATIONS:
Pressure display range:

29 InHg to 600 psig (-98kPa to 4134 kPa)
(+/- 1 PSI to 200 psi, 0.5% to 600 psi)

Temperature display range:

-40°F to 200°F (-40°C to 93°C)

Operating temperature:

-10°F to 120°F (-12°C to 49°C)
(+/- 1°F * 32°F/120°F, +/- 1.5°F * -10°F/32°F)

Maximum overpressure:

800 psig (5512 kPa)

Battery life and type:

100 hours/ 9vAlkaline battery

Auto-shutoff time:

60 minutes (extended 60 minutes by upper button action)

Refrigerant data source:

NIST REFRPRO software and manufacturers data

Uses one 9v Alkaline battery

(not included)

EXTENDING

AUTO-SHUTOFF TIME

Extend time by 60 minutes by
pressing upper button.

SUPERHEAT

TEMPERATURE

SENSOR

2

1

Only a properly charged unit will provide the owner
with the design SEER for maximum energy efficiency.

SUPERHEAT, TEMPERATURE,
SUBCOOLING AND PRESSURE

PUSH once to toggle between displays
PUSH 2 times to recall High, Low & Average

Hold down to clear memory.

ON/OFF

PUSH once to “Turn On”
Display shows LAST refrigerant used.
HOLD down to "Turn Off"
PUSH 2 times to select 1 hour or 24 hour auto-off mode

REFRIGERANT SELECTION

PRESS once at any time to display current refrigerant.
Continue pressing to scroll the refrigerant list.
(See list of refrigerants on page 4.)

APPLICATION TIPS:
Allow the manifold to Zero at Turn-On:

The manifold displays will zero (CAL) each time the

manifold is turned on open to atmosphere. Zeroing the gauge
compensates the Pressure display for changes in (1) Altitude
and (2) Barometric pressure.

Pressure Calibration

Don’t be alarmed if your manifold gauge does not agree

with your mechanical gauges. The digital manifold is
calibrated with a very accurate pressure and is not affected
by vibration, motion or position.

Extending On-Time

The digital manifold will turn off automatically after 60

minutes to save battery life.

If any button is touched the digital manifold will stay on for

another 60 minutes.

Over/Under-Range Indicator

Pressures or temperatures below or above the rated

ranges will cause a “1” to be displayed.

Low Battery Indicator

Low batteries will be indicated by a blinking display.

Batteries For Low Temperature Applications

Using the gauge in a low temperature conditions will

shorten battery life. Change to the 9 volt Lithium battery
(Radio Shack 23-665) to solve this problem.

SH-35N

(°F)

and SH-36N

(°C)

SUPERHEAT and SUBCOOLING GAUGE
OPERATING INSTRUCTIONS