Outsideglz-sill-flashing, Da c b f – Oldcastle BuildingEnvelope FG-3000 User Manual

Page 10

Advertising
background image

OUTSIDE GLAZE SILL FLASHING

INSTALLATION AND PERIMETER SEAL

APPLY SEALANT ALONG LENGTH OF SUB SILL

AT AREAS A & B.

LAY FLASHING ON SLAB AND SHIM ONLY AT LOW

AREAS. RESEAL AT SHIM AREAS.

SPACE BETWEEN SILL AND FLASHING (C) TO BE

CONTINUOUSLY SEALED EXCEPT FOR 1/2"-3/4"

SPACE UNDER VERTICAL MULLIONS FOR WEEPAGE.

PRIOR TO INSTALLING FRAME, APPLY SEALANT

CONTINUOUSLY ALONG SILL FLASHING (D).

THIS WILL PROVIDE CONTINUOUS SEAL

BETWEEN SILL AND SILL FLASHING.

THE QUALITY OF THE INSIDE AND OUTSIDE

PERIMETER SEALS (C AND E) MAY BE IMPROVED

BY USING FG-2188 RIGID PVC FILLER.

THE PART MAY BE USED IN FULL LENGTHS OR CUT

INTO PIECES. ITS PURPOSE IS TO PROVIDE

SUPPORT FOR THE BACKER ROD REGARDLESS

OF JOINT OR SIZE. PERIMETED SEAL (F) IS FOR

COSMETIC PURPOSES AND IS OPTIONAL.

FG-2000-FP-3 PART #: 7944

D

A

C

B

F

NOTE: 1/2"- 3/4" WEEP HOLE

REQUIRED IN SEALANT AT

FLASHING (C)AT CENTER

LINE OF MULLION.

E

E

E

E

FG-2122

4" LONG

(PARTS SOLD IN

STOCK LENGTHS.)

9

JULY 2011

Phone: 1-866-OLDCASTLE (653-2278)

Web Address: www.oldcastlebe.com

F L U S H G L A Z E S E R I E S 3 0 0 0 I N S T A L L A T I O N M A N U A L