INSIDE GLAZE

GLAZING PROCEDURE

MITER HORIZONTAL GASKE

T

TO FIT VERTICAL GASKET.

15

0

NOTE:

FIRST, WET

BOTTOM OF SETTING

BLOCKS WITH SOAPY

WATER. ONCE GLASS IS SET,

PUSH AGAINST GASKET AT

SETTING BLOCK AREA.

FAILURE TO DO SO MAY CAUSE

DIAGONAL CRACKS TOWARDS

SETTING BLOCKS DUE TO GLASS

BENDING WHILE INSTALLING

GASKET(S) IN CORNERS.

VERTICAL GASKETS

RUN THRU.

HP-17

PART #: 10267

FG-1133

PART #: 364

FG-1000-FP-2

PART #: 6887

SET IN PLACE

WITH SEALANT.

GLAZING INSTALLATION INSTRUCTIONS

GLASS SIZE

7/8" OVER DAY LIGHT OPENING

SETTING BLOCK

SET AT 1/4 POINT OR 1/8 POINT OF HORIZONTAL LENGTH

DEPENDING ON LITE SIZE.

WATER DIVERTERS

GLAZE FROM BOTTOM TO TOP. INSTALL WATER DIVERTERS IN

HORIZONTAL ABOVE, AFTER LITE BELOW IS IN POSITION.

GLAZING GASKET

GASKET MAY BE INSTALLED ON ONE OR BOTH SIDES

SIMULTANEOUSLY. PROVIDE 3/8" ADDITIONAL GASKET

FOR EACH FOOT OF DAYLIGHT OPENING TO PROVIDE

ADEQUATE COMPRESSION FOR THE GLAZING INFILL.
NOTE: CLEAN GASKET WITH ISOPROPYL ALCOHOL PRIOR TO

SEALING CORNERS.

17

JULY 2011

Phone: 1-866-OLDCASTLE (653-2278)

Web Address: www.oldcastlebe.com

F L U S H G L A Z E S E R I E S 3 0 0 0 I N S T A L L A T I O N M A N U A L