Pg 2 – Cleveland Range Convotherm Combination Oven-Steamer Electric 6.20 User Manual

Page 70

Advertising
background image

• If the ground is not found 220 VAC is sent from terminal 7 on connector X12

on the Control Board (A10) to the fill solenoid (Y3)

• The fill solenoid opens and the generator is filled until both probes are

grounded.
◊ If the top probe becomes ungrounded for more that 5 seconds the fill

solenoid (Y3) will energize.

◊ If the bottom probe becomes ungrounded the combi will fill immediately

and the combi will not heat

d

When the terminal 2 on connector X15 is grounded

• 220 VAC is sent from terminal 4 of connector X12 on the Control Board

(A10) through the normally closed auxiliary contacts of K4 to the coil of
Contactor K1 until the steam generator get to 190 degrees F (probe B4).
◊ The contactor K1 closes and 220 VAC is sent to the 9.4 KW element (E1)

◊ The normally closed auxiliary contact of K1 opens preventing the Hot Air

Contactor K4 from energizing

• 220 VAC is sent from terminal 8 of connector X11 on the Control Board

(A10) through the normally closed auxiliary contacts of K44 to the coil of
Contactor K2 until the steam generator get to 190 degrees F (probe B4).
◊ The contactor K2 closes and 220 VAC is sent to the 6.27 KW element

(E2)

◊ The normally closed auxiliary contact of K2 opens preventing the Hot Air

Contactor K4 from energizing

4

With the combi in the steam mode with time on the timer, the door closed and the

start switch is depressed
a

The front display will include a lighted bar under the steam symbol

• When the heat circuit is energized the heat symbol will be energized

• The cooking mode symbol will be energized.

• The time display will invert and begin to count down.

b

The fan circuit is energized

NOTE: If the temperature is less than 212 degrees F than fan will be pulsed

on for 2 seconds every 60 seconds after the cabinet set temp (B6).

• If the combi fan is in the normal setting 220 VAC is sent from terminal 5 on

connector X11 through the normally closed auxiliary contacts of contactor
K57 to the coils of contactors K55 and K56
◊ The K55 and K56 contactors close sending 220 VAC through the Q56

overload to the motor and the motor turns at a high speed.

◊ The normally closed auxiliary contacts of both K55 and K56 open

preventing the K57 contactor from energizing.

• If the combi fan is in the reduced setting 220 VAC is sent from terminal 6 on

connector X11 through the normally closed auxiliary contacts of contactors
K55 and K56 to the coil of contactor K57
◊ The K57 contactor closes Sending 220 VAC through the Q57 thermal

overload to the motor and the motor turns at a reduced speed.

◊ The normally closed auxiliary contacts of K57 open preventing the K55

and K56 contactors from energizing.

62

Advertising
This manual is related to the following products: