BECKETT CLEANCUT

BECKETT CLEANCUT INSTALLATION INFORMATION

INSTALLATION INFORMATION

GENERATION INFORMATION - ALL SYSTEMS

IMPORTANT INFORMATION Long or oversized inlet lines may
require the pump to operate dry during initial bleeding period. In
such cases, the priming may be assisted by injecting fuel oil in
the pump gearset. Under lift conditions, lines and fi ttings must be
air tight. To assure this, oil-resistant pipe joint compound may be
applied to both the used and unused inlet and both return fi ttings.

2-

2-STAGE

STAGE FUEL UNIT

FUEL UNIT

Part No. 21941

Part No. 21941

Please read and understand the manual supplied with this equip-

ment. This equipment must be installed, adjusted and put into
operation only by a qualifi ed individual or service agency that is:

Licensed or certifi ed to install and provide technical service
to oil heating systems.
Experienced with all applicable codes, standards and ordi-
nances.
Responsible for the correct installation and commission of
this equipment.
Skilled in the adjustment of oil burners using combustion
test instruments.

The installation must strictly comply with all applicable codes,

authorities having jurisdiction and the latest revision of the Na-
tional Fire Protection Association Standard for the installation of
Oil-burning Equipment, NFPA 31 (or CSA-B139 and CSA-B140
in Canada).

Regulation by these authorities take precedence over the general

instructions provided in this installation manual.

y

y

y

y

Incorrect installation, adjustment, or mis-

use of this burner could result in severe
personal injury, death, or substantial prop-
erty damage from fi re, carbon monoxide
poisoning, soot or explosion.

Professional Service Re-

quired

WARNING

!

Oil Leak & Fire Hazard

WARNING

!

The inlet and return line pressures must not exceed 3 psig,
or pump seal damage and oil leaks could result! See NFPA
31-25, 8.6.3.
Do not use a check valve in the inlet line of a 1-pipe system
(with or w/o a boost pump), or in the return line of a 2-pipe
system.
NFPA 31-25, 8.5 states that ‘A return line from a burner or
pump to a supply line shall have no valves or obstructions
and shall enter the top of the same tank.’
Check valve fl ow restriction in a return line can elevate
pressures and damage the fuel unit seals.
Dangerous thermal expansion of oil trapped by an inlet
line check valve can create extreme pressures that damage
fuel unit seals, line fi ttings, inlet fi lters, gauges and other
components. A properly installed vacuum safety valve, such
as Suntec PRV-38, having accumulator effect and pressure
relief to tank is acceptable in the inlet line.
Do not use tefl on tape or compression fi ttings.

y

y

y

y

y

y

SINGLE STAGE

SINGLE STAGE FUEL UNIT

FUEL UNIT

Part No. 21844

Part No. 21844

This pump must be used with

a controlling device that pro-

vides a valve on delay (pre-purge).

!

!

CAUTION

MOUNTING POSITION Beckett CleanCut fuel unit may be
mounted in any position (except upside-down during single pipe
installation).

VACUUM CHECK A Vacuum Gauge may be installed in either
of the 1/4” NPT inlet ports. The Beckett CleanCut pump should
be used where the vacuum does not exceed 6” hg. single pipe
and 12” hg. two pipe. The Beckett CleanCut XL pump should be
used where the vacuum is less than 17” hg. Remember, running
vacuum is the total of all pressure drops (eP) in the system from
tank to inlet of pump.

PRESSURE CHECK When a pressure check is made use either
the BLEED PORT OR NOZZLE PORT.

CUTOFF CHECK To check cutoff pressure, dead head a pres-
sure gauge in nozzle port. Run burner for short period of time.
Shut burner off. The pressure will drop and hold above zero.

MOUNTING PUMP

(If the shutter screw interferes

with the solenoid on the fuel unit)

To install a CleanCut fuel unit on chassis with existing shutter tab
see Figure 2 and follow these steps:

Remove existing fuel unit and solenoid valves, if applicable, and
appropriately dispose of them.

Note the air setting of the shutter, then remove the air shutter, set
the shutter aside to be reinstalled.

R.W. BECKETT CORPORATION

U.S.A.: P.O. Box 1289 · Elyria, Ohio 44036

Canada: R.W. Beckett Canada, Ltd. · Unit #3, 430 Laird Road · Guelph,

Ontario N1G 3X7

Form Number 61583 R07 © 2007 R.W. Beckett Corporation 10/07

DO NOT INSTALL

THE TOP SHUTTER

SCREW IF IT INTER-

FERES WITH THE

SOLENOID ON THE

FUEL UNIT.

SHUTTER TAB

(REMOVE)

LOWER SHUT-

TER SCREW

Figure 2

O

O

4 GPH 100-150 PSI 3450 RPM

3 GPH 150-200 PSI 3450 RPM

VALVE ON DELAY

NO. 2 & LIGHTER FUEL

USE ONLY WITH

INLET

BY-PASS

Exclusively for Beckett

Made by Suntec

INLET

NO. 2 FUEL

A2EA-6520

Beckett

FIGURE 1

Figure 1