Beckett AquaSmart 2N1 sensor User Manual

Aquasmart

Advertising
background image

AQUASMART

TM

2-IN-1 SENSOR (Temperature & Presence of Water)

Installation Instructions

PARTS:

For proper operation, there must be

a secure electrical bond between

the green sensor wire from the sensor and the boiler

metal vessel in direct contact with the boiler water.

Failure to secure an electrical bond will result in the

AquaSmart locking out and displaying, “LOCKOUT

- LOW WATER”.

Explosion,
Burn and Scald Hazards

Excessive water temperatures could cause explosion,

burns, scalding, pressure relief fl ooding and fi tting leaks.

The 2-in-1 Sensor shall only be installed by a trained
professional.

The sensor must be installed in the proper location for
correct low water cut-off (LWCO) operation in
accordance with the Boiler Manufacturer’s instructions.

The 2-in-1 sensor body is installed directly into the
boiler wall tapped hole in place of an immersion well.

Carefully follow the outlined procedures for temperature
sensor installation to ensure accurate water temperature
sensing and effective control operation.

Make sure the plumbing for domestic hot water has anti-
scald valve protection.

Follow all applicable safety codes, rules and guidelines
for installing an immersion well. Improper installation can
result in the Boiler overheating.

y

y

y

y

y

y

Do not use in steam applications. For use in hot water boilers or water
heaters only. Do not use outside of the intended use and specifi cations.

Technical Specifi cations

Storage Temp. Range:

Operating Temp. Range:

Maximum Pressure:

Installation(screw-in)Torque Range:

-40°F to 250°F

32°F to 250°F

250 PSIG

185-200 in/lbs

Leak, Burn, and Scald
Hazards

Incompatible thread sealants could severely damage

the sensor threads.

Only use Tefl on

®

Tape or Rectroseal

®

No. 5

®

(soft-set).

DO NOT use any anaerobic fast-setting sealants such
as, but not limited to, Loctite

®

, Leak Lock

®

,

Permatex

®

, or Gasoila

®

.

Call RWB Technical Services at 1(800)645-2876 to
confi rm, if unsure.

y
y

y

Installation Instructions on back.

(1) 76002N1SXX 2-IN-1 Sensor

(1) 32704 Pipe Clamp for sensor ground

(1) 3214771 36” Green Ground Wire

Part #

Lead Length

Insulation Depth

(A)

Insertion Depth

(B)

76002N1S01

8-1/4”

1-1/2”

1-5/8”

76002N1S02

6-1/4”

3-1/2”

1-5/8”

76002N1S05

5.0”

4-3/4”

1-5/8”

76002N1S06

8-1/4”

1-1/2”

7/8”