Sediment traps, A warning, Awarning – Kenmore POWER MISER 153.33616 User Manual

Page 16

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed

14 inch water column (3.5kPa) for natural and propane gas

{L.P.). The minimum inlet gas pressure listed on the rating
plate is for the purpose of input adjustment. If the gas control
valve is subjected to pressures exceeding 1/2 pound per square
inch (3.5kPa), the damage to the gas control valve could result
in a fire or explosion from leaking gas.

If the main gas line shut-off serving all gas appliances is used,

also turn “OFF” the gas at each appliance. Leave all gas
appliances shut “OFF" until the water heater installation is
complete.

A gas line of sufficient size must be run to the water heater.
Consult the current edition of National Fuel Gas Code ANSI
Z223.1/NFPA 54 and your gas supplier concerning pipe size.

There must be:

• A readily accessible manual shut off valve in the gas supply

line serving the water heater, and

• A drip leg (sediment trap) ahead of the gas control valve to

help prevent dirt and foreign materials from entering the
gas control valve.

• A flexible gas connector or a ground joint union between the

shut off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open
flame. Rinse off soapy solution and wipe dry.

The minimum inlet gas pressure shown on the rating plate is
that which will permit firing at the rated input.

A WARNING

Breathing Hazard - Carbon Monoxide Gas

High altitude orifice must be installed

for operation above 3,300 ft. (1,006 m)

or 5,500 ft, (1,075 m) for a high altitude
models.

Contact a qualified installer or service
agency.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand Instruction manual.

If a standard mode! is installed above 3,300 feet (1,006 m) or a

high altitude model is installed above 5,500 feet (1,676 m) the
input rating should be reduced at the rate of 4 percent for each

1,000 feet (305 m) above sea level which requires replacement

of the burner orifice in accordance with National Fuel Gas Code
ANSI Z223.1/NFPA 54. Contact your local Sears Service Center
or local gas supplier for fljrther information.

Failure to replace the standard orifice with a high altitude orifice

when installed at elevations above 3,300 feet (1,006 m) or
above 5,500 feet (1,676 m) for high altitude model) could result

in improper and inefficient operation of the appliance, producing
carbon monoxide gas in excess of safe limits, which could
result in serious injury or death. Contact your local Sears Service
Center or local gas supplier for any specific changes which
may be required in your area.

AWARNING

Fire and

Explosion

Hazard

Use joint compound or tape

compatible with propane.

Leak test before operating
heater.

Disconnect gas piping and
shut-off valve before pressure

testing system

Use pipe joint compound or teflon tape marked as being
resistant to the action of petroleum (Propane [L.P.]) gases.

The appliance and its gas connection must be leak tested
before placing the appliance in operation.

The appliance and its individual shut-off valve shall be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of

1/2 pound per square inch (3.5kPa). it shall be isolated from

the gas supply piping system by closing its individual manual

shut-off valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2 pound
per square inch (3.5kPa).

Connecting the gas piping to the gas control valve of the water
heater can be accomplished by either of the two methods
shown in Figures 19 and 20.

Sediment Traps

AWARNING

Fire and Explosion Hazard

Contaminants in gas lines can
cause fire or explosion.

Clean all gas piping before

installation.

install drip leg in accordance

with NFPA54.

Contaminants in the gas lines may cause improper operation
of the gas control valve that may result in fire or explosion.
Before attaching the gas line be sure that all gas pipe is clean
on the inside. To trap any dirt or foreign material in the gas
supply line, a drip leg (sometimes called a sediment trap)
must be incorporated in the piping. The drip leg must be readily
accessible, install in accordance with the Gas

Piping

section.

Refer to the current edition of the National Fuel Gas Code,

ANSIZ223.1/NFPA54.

16

Advertising