Installation instructions (cdnt^d), Temperature-pressure relief valve, Awarning – Kenmore POWER MISER 153.330551 User Manual

Page 12: Relief valve opening

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installation Instructions (cdnt^d)

Temperature-Pressure Relief Valve

AWARNING

At the time of manufacture this water heater was provided
with a combination temperature-pressures relief valve certified
by a nationally recognized testing laboratory that maintains
periodic inspection of production of listed equipment or mate­
rials, as meeting the requirements for Relief Valves and

Automatic Gas Shutoff Devices for Hot Water Supply Systems,
and the latest edition of ANSI Z2I.22 and the code require­
ments of ASME, If replaced, the valve must meet the require­
ments of local codes, but not less than a combination tempera­
ture and pressure relief valve certified as meeting the require­
ments for Relief Valves and Automatic Gas Shutoff Devices for

Hot Water Supply Systems, ANSI Z21.22 by a nationally recog­
nized testing laboratory that maintains periodic inspection of

production of listed equipment or materials.
The valve must be maiiced with a maximum set pressure not

to exceed the marked hydrostatic working pressure of the

water heater (ISO IbsJ^, in.) and a discharge capacity not less
than the water heater input rate as shown on the model rating

plato. (Electric heaters - watts divided by 1000 x 34IS eoual
BTU/Hr. rate.)

^

Your local jurisdictional authority, while mandating the use of a

temperature-pressure relief valve complying with ANSI Z2I.22

and ASME, may require a valve model different from the one

furnished vrith the water heater.

Compliance with such local requirements must be satisfied by

the installer or end user of the water heater with a locally pre­
scribed temperature-pressure relief valve installed in the desig­

nated opening in the vrater heater in place of the factory fur­
nished valve.
For safe operation of the water heater, the relief valve must not

be removed from it^ designated opening or plugged.
The temperature-pressure relief «üve must be installed directly

into toe fitting of the water heater designated for the relief valve.

Position the valve downward »id provide tubing so that any dis­

charge will exit only within

6

inches above, or at any distance

below the structui^ floor. Be certain that no contact is made
with any live electrical part The discharge opening must not be
blocked or reduced in size under any circumstances. Excessive
length, over 30 feet, or use of more than four elbows can cause
restriction and reduce toe discharge capacity of the valve.
No valve or other obstruction is to be placed between toe relief

valve and toe tank. Do not connect tubing directly to discharge
draih unless a

6

" air gap is provided. To prevent bodily injury, haz­

ard to life, or property dam^, the relief valve must be allowed

to discharge water in quantities should circumstances demand. If
the discharge pipe is not connected to a drain or other suitable

means, toe water flow may cause property damage.

Thé Discharge Pipe:

• Must not be smaller in size than toe outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

■ Must not be plugged or blocked.
• Must be of material listed for hot water distribution.
• Must be installed so as to allow complete drainage of both

the temperature-pressure relief valve, and the discharge
pipe.

• Must terminate at an adequate drain.
• Must not have any valve between the relief valve and tank.

AWARNING

The temperature-pressure relief valve must be manually
operated at least once a year. Caution should be taken to
ensure that ( I ) no one is in front of or around the outlet of

the temperature-pressure relief valve discharge line, and (

2

)

the water manually discharged will not cause any bodily

injury or property damage because the water may be

extremely hot.

If after manually operating the valve, it fóls to completely
reset and continues to release water, immediately close the

cold water inlet to the water heater, follow the draining

instructions, and replace the temperature-pressure relief

valve with a new one.

RELIEF VALVE OPENING

At the time of nranufacture, this water heater was prodded with a combination lem-

perature-pressure relief valve listed as complying with the standard for relief valves

and automatic gas shut-off devices for hot water supply systems, ANSI Z2I.22. For

safe Operation of the water heater, the reiief valve must not be removed from its des­
ignated point of installation or plugged.

ibuf local jurisdictional authority, while mandating the use of a temperature-pressure

relief valve complying with ANSI Z2I.22 and ASME, may require a valve model differ­

ent from the one furnished with the water heater.

Compliance with such local requirements must be satisfied by the instatfer or end user

of the water heater with a locally prescribed temperature-pressure relief valve
installed in the designated opening in the water heater.

See manual heading -‘Temperature-Pressure Relief Valves" for installation and mainte­
nance of relief valve, discharge line, and other safety precautions.

12