Chemical vapor corrosion of the flue, blower assembly and vent system
may occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air conditioner
refrigerants, swimming pool chemicals, calcium and sodium chloride,
waxes, bleach and process chemicals are typical compounds which
are potentially corrosive.

A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 10 and 11)

The confined space shall be provided with two permanent openings

communicating directly with an additional room(s) of sufficient volume
so that the combined volume of all spaces meets the criteria for an
unconfined space. The total input of all gas utilization equipment installed
in the combined space shall be considered in making this determination.

Each opening shall have a minimum free area of one square inch per
1,000 Bfu per hour (22 cm^/kW) of the total input rating of all gas utilization

equipment in the confined space, but not less than 100 square inches
(645 cm^). One opening shall commence within 12 inches
(31 cm) of the top and one commencing within 12 inches (31 cm) of the
bottom of the enclosures.

VENT THROUGH

ROOF

OPENINGS

2, When communicating with the outdoors through vertical ducts, each

opening shall have a minimum free area of 1 square inch per 4,000

Btu per hour (5.5 cm^/kW) of total input rating of all equipment in the

enclosure, see Figure 13.

3. When communicating with the outdoors through horizontal ducts,

each opening shall have a minimum free area of 1 square inch per
2,000 Btu per hour (11 cmVkW)) of total input rating of aii equipment

in the enclosure, see Figure 14.

VENTILATION LOUVERS

(each end of attic)

VENT THROUGH

ROOF

INLET AIR DUCT

(ends 1" above floor)

4.

FIGURE 13.

When ducts are used, they shall be of the same cross-sectional
area as the free area of the openings to which they connect. The

minimum short side dimension of rectangular air ducts shall not be
less than 3 inches (7.6 cm), see Figure 14.

11

.

B. ALL AIR FROM OUTDOORS: (See Figures 12,13 and 14)

The confined space shall be provided with two permanent openings,

one commencing within 12 inches (31 cm) of the top and one
commencing within 12 inches (31 cm) from the bottom of the enclosure.
The openings shall communicate directly, or by ducts, with the outdoors
or spaces (crawl or attic) that freely communicate with the outdoors.

1. When directly communicating with the outdoors, each opening shall

have a minimum free area of 1 square inch per 4,000 Btu per hour
(5.5 cm^/kW) of total input rating of all equipment in the enclosure,
see Figure 12.

VENT THROUGH

ROOF

FIGURE 14.

VENTILATION LOUVERS

(each end of attic)

VENT THROUGH

ROOF

VENTILATION LOUVERS

12.

5. Louvers and Grilles: In calculating free area, consideration shall be

given to the blocking effect of louvers, grilles or screens protecting
openings. Screens used shall not be smaller than 1/4 inch

(6.4 mm) mesh. If the free area through a design of louver or grille
is known, it should be used in calculating the size opening required

to provide the free area specified. If the design and free area is not

known, it may be assumed that wood louvers will be 20-25 percent

free area and metal louvers and grilles will have 60-75 percent free
area. Louvers and grilles shall be fixed in the open position or

interlocked with the equipment so that they are opened automatically

during equipment operation.

6. Special Conditions Created by Mechanical Exhausting or Fireplaces:

operation of exhaust fans, venfiiation systems, clothes dryers or
fireplaces may create conditions requiring special attention to avoid

unsatisfactory operation of installed gas utilization equipment.