Important information about this water heater, Installation checklist – Kenmore ELITE 153.33264 User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

IMPORTANT INFORMATION ABOUT THIS WATER HEATER

This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor ignition incident.
The new technology used in meeting these standards makes this product more sensitive to installation errors. Please review the following
checklist and make any required installation upgrades or changes.

Questions? Contact Sears at (1-800-469-4663).

Installation Checklist

Water Heater Location

Water heater location is important and can affect system
performance. Please check the following:

□ Installation area free of corrosive elements and flammable

materials.

□ Centrally located with the water piping system (For new

installations). Located as close to the gas piping, vent pipe

system and 120VAC outlet as possible.

□ Located indoors and in a vertical position. Protected from

freezing temperatures.

□ Proper clearances from combustible surfaces

maintained and not installed directly on a carpeted floor.

□ Provisions made to protect the area from water damage.

Metal drain pan installed and piped to an adequate drain.

□ Sufficient room to service the water heater. See Clearances

and Accessibility section of this manual.

□ Water heater not located near an air moving device.

□ Is the installed environment dirty (excessive amounts of lint,

dirt, dust, etc.)? If so, the air intake chamber louvers located
on the side of the water heater will need to be cleaned
periodically. Refer to the maintenance section of your water
heater’s manual for information on cleaning the “Air Intake
Chamber Screen”.

Combustion Air Suppiy and Ventiiation

Check for sufficient combustion air supply. Insufficient air for the
combustion of gas will result in a inferior burner flame “yellow-
lazy”, thereby allowing smoking and carbon formation (sooting) to
build up in the combustion chamber.

Is the water heater installed in a closet or other small, enclosed

space? If so:

□ Are there openings for make-up air to enter and exit the

room/area?

□ Are the openings of sufficient size? Remember, if there are

other gas-fired or air-consuming appliances in the same
room, you need more make-up air. Refer to the Location

Requirements section of this water heater manual for

specific requirements.

Fresh air not taken from areas that contain negative pressure
producing devices such as exhaust fans, dryers, fireplaces, etc.

□ Is there a furnace/air handler in the same room space as

the water heater? If so, has a return air duct system been
attached that exits the room? If so, check for leaks on the
air duct system. If no air duct system is present, correct

immediately by contacting a local Heating, Ventilation, Air­
Conditioning & Refrigeration (HVAC-R) authorized service
provider.

□ Fresh air supply free of corrosive elements and

flammable vapors.

□ Ductwork is the same cross-sectional area as the

openings.

Vent Pipe System

Check for proper drafting at the water heater draft hood. Refer
to the “Checking the Draft” section of this manual for the test
procedure. If the procedure shows insufficient draft is present,
please check the following.

Draft hood properly installed.

Vent connectors securely fastened with screws and
supported properly to maintain six inch clearance.

Vent connector made of approved material and sized

correctly.

Vent pipe system installed according to all local and state

codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current
edition.

Flue baffle properly positioned in the flue tube.

Check the vent system for restrictions/obstructions and
check the vent termination height. Refer to the “Combustion

Air and Ventilation” section of this water heater manual for
specific requirements.

Recheck for sufficient combustion air supply.

Water System Piping

Temperature and pressure relief valve properly installed with
a discharge line run to an open drain and protected from
freezing.

All piping properly installed and free of leaks.

Heater completely filled with water.

Closed system pressure build-up devices installed.

Mixing valve (when applicable) installed per manufacturer’s
instructions (See Water Temperature Regulation section).

Gas Suppiy and Piping

Gas type is the same as that listed on the water heater rating
plate.

Gas line equipped with shut-off valve, union, and drip leg.

Use pipe joint compound or teflon tape marked as being
resistant to the action of petroleum gases.

Adequate pipe size and approved pipe material.

An approved noncorrosive leak detection solution used
to check all connections and fittings for possible gas leaks.

Correct any leak found.

Eiectricai Suppiy

Water heater to be located as close as possible to a 120VAC
outlet (extension cord is not allowed).

Electrical supply installed according to all local and state
codes or, in the absence of local and state codes, the
“National Electrical Code”, ANSI/NFPS 70 current edition.

11

Advertising
This manual is related to the following products: