Burner Does Not Start When Thermostat Calls For Heat
PRELIMINARY CHECKS

1. Ensure all limit switches are closed.

2. Ensure safety switch is reset.
3. Check for the proper line voltage at the oil primary.

Proceed as follows after completing the preliminary checks.

CORRECTIVE ACTION

PROCEDURE

BURNER STARTS

BURNER DOES NOT START

1. Jumper the thermostat

terminals:

• Low voltage thermostat
at oil primary
• Line voltage thermostat
at thermostat

Trouble in the thermostat circuit.
Check the thermostat and

wiring connections.

Trouble is in the bimetal detector or

the oil primary. Put contacts in step

by pulling drive shaft lever out 1/4
inch and releasing. Refer to Fig. 8.

2. Jumper thermostat terminals

to start burner.

Bimetal detector and oil primary

are OK.

Clean the bimetal detector contacts
and timer contacts (if provided).

Go to step 3.

3. Jumper thermostat terminals

to start burner.

Bimetal detector and oil primary

are OK.

Go to step 4.

4. Jumper the thermostat

terminals and jumper the

normally closed contacts.

Reclean the bimetal detector

contacts again and recheck
by jumpering the thermostat

terminals. If the burner starts,

bimetal detector and oil primary
are OK.

Go to step 5.

5. Jumper the thermostat

terminals and jumper the

R and B terminals on the

oil primary.

Check for broken wires, loose

connections between the bimetal
detector and the control.

Repair and recheck by jumpering

the thermostat terminals. Replace
the bimetal detector if necessary.

Replace the oil primary and perform
Startup and Checkout procedures.

Burner Starts, Flame Is Established. Then Safety Switch Locks Out on Safety.

PRELIMINARY STEPS;

1. Reset the safety switch.

2. Clean bimetal detector contacts.

Proceed as follows after completing the preliminary checks.

CORRECTIVE ACTION

PROCEDURE

BURNER KEEPS RUNNING

BURNER LOCKS OUT

1. Jumper thermostat

terminals to start burner.

• Low voltage thermostat
at oil primary
• Line voltage thermostat
at thermostat

Bimetal detector and oil primary
are OK.

• Clean the drive shaft, remove

the detector and clean bimetal

element. Replace the detector.

• Check the detector location. If

the stack temperature is below

300° F [149° C], replace the bimetal

detector.

2. Reset the safety switch

and jumper the thermostat

terminals to start the burner.

Bimetal detector and oil primary

are OK.

Replace the oil primary and perform
Startup and Checkout procedures.

Honeywell Inc.

U.S.A.: 1885 Douglas Drive N.

Golden Valley, MN 55422-4386

CANADA: 740 Ellesmere Road

Scarborough, Ontario M1P 2V9

International Sales Offices in all principal cities of the world. Manufacturing in

Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands,
Spain, Taiwan, United Kingdom, U.S.A.

PRINTED IN U.S.A.

QUALITY IS KEY

Advertising
This manual is related to the following products: