DO NOT FORCE THE COLLAR OF THE MOUNTING FLANGE PAST THE STOP.

FIG. 2—MOUNTING AND LOCATION CONSIDERATIONS.

• Locate the control between the boiler or furnace and

draft regulator.

• Locate the control as near as possible to the boiler

or furnace.

• If mounting in an elbow, locate the element near the

outer curve where the hottest gases flow.

• Do not locate the element where the temperature

may exceed 1000° C [556° С].

2. Cut a 1 -3/8 inch [35 millimeter] hole in the stack at the

location desired.

3. Drill two holes and fasten the mountihg flange using

the screws provided. The flange should fit the mounting

surface snugly, but it may be bent to fit a different radius
stack or flattened to fit aflat surface. Do not force the collar
or mounting flange past the stop.

4. Insert the bimetal element at the center of the stack

in direct path of the hottest flue gasses.

5. Tighten the lockscrew.

WIRING

Follow the appliance manufacturer’s instructions, if

available. Otherwise, follow the wiring diagrams shown in
Fig. 3 through 7.

FIG. 3—RA116A WIRING DIAGRAM WITH A 24V, 3-

WIRE THERMOSTAT.