Trane 18-BC55D1-2 User Manual

Heat pumps, Bc55d1-2, Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

18-BC55D1-2

Heat Pumps

4TWX6

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.

These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation. All phases of
this installation must comply with NATIONAL, STATE

AND LOCAL CODES. Should further information be

desired or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor,

A. GENERAL

The following instructions cover 4TWX6 Heat Pump Units,

NOTICE:

These outdoor units may be used

with

indoor units

equipped

with Thermostatic Expansion

Valve

only.

A

WARNING

These units use

R-410A

refrigerant which operates at 50 to

70% higher pressures than R-22. Use only R-410A approved
service equipment. Refrigerant cylinders are painted a “Rose”
color to indicate the type of refrigerant and may contain a

“dip” tube to allow for charging of liquid refrigerant into the

system. All R-410A systems use a POE oil that readily absorbs

moisture from the atmosphere. To limit this “hygroscopic”

action, the system should remain sealed whenever pos­
sible. Never break a vacuum with air and always change the

driers when opening the system for component replacement.

Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.

To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power
available must agree with that listed on the nameplate.

The Weathertron® Heat Pump has been designed and
manufactured to withstand and operate in severe winter
conditions. However, there are precautionary steps which
should be taken at the time of installation which will help
assure the efficient operation of the unit. It is recom­
mended that
these precautions be taken for units

being installed in areas where snow accumulation and
prolonged below freezing temperatures occur.

1, Units should be elevated 3 to 12 inches above the pad or

rooftop, depending on local weather. This additional
height will allow better drainage of snow and ice (melted
during defrost cycle) prior to its refreezing. This should
prevent a build-up of ice around the unit which occurs
when unit is not elevated. Insure that drain holes in

A

CAUTION

UNIT CONTAINS R-410A REFRIGERANT!

R-410A OPERATING PRESSURE EXCEEDS THE
LIMIT OF R-22. PROPER SERVICE EOUIPMENT IS
REOUIRED. FAILURE TO USE PROPER SERVICE

TOOLS MAY RESULT IN EOUIPMENT DAMAGE OR

PERSONAL INJURY.

SERVICE

USE ONLY R-41OA REFRIGERANT AND

APPROVED POE COMPRESSOR OIL.

unit base pan are not obstructed preventing
draining of defrost water.

2, If possible, avoid locations that are likely to accumulate

snow drifts. If not possible, a snow drift barrier should be
installed around the unit to prevent a build-up of snow
on the sides of the unit and should be of sufficient
distance from the unit to prevent restriction of airflow to
and from the unit. Also allow for proper maintenance
space. The barrier should be constructed of materials

which will blend in with the building design,

3, Avoid locating the unit where condensation and freezing

of defrost vapor may annoy the customer. For instance.

Advertising
This manual is related to the following products: