Installation Instructions

1. Choose a mounting location in the control panel within reach of

the leads provided. Use 50/50 water to isopropyl alcohol to

clean the mounting surface. After the surface has dried, remove

protective covering from the tape. Mount unit as shown on

control panel illustration. Route wires to the appropriate

terminals as noted below.

2. Connect 405-05 trigger wires to the fire alarm output terminals.

Observe polarity. [Gray wire to positive (+) and White wire to

negative (-)].

3. Connect 405-05 incoming power wires to the smoke detector

power source. [White-Red to (+) and White-Black to (-)].

4. Connect 405-05 outgoing power wires to the smoke detector

power in terminals. [Red to (+) and Black to (-)].

5. Connect the smoke detector initiating circuit (alarm loop) to the

alarm control.

6. Maintenance: no maintenance is required.

secondary
power

Bell
Circuit

+

-

+

-

zone 01 zone 02 zone 03 zone 04 zone 06 zone 08

.

Testing: 405-05

1. Test in accordance with NFPA 72 Chapter 7 Test Methods &

Frequencies, interfacing equipment.

2. To test the 405-05 initiate an alarm with smoke or approved

test method on any detector connected to the control panel

via the 405 relay. In alarm, detectors that have responded to

smoke or test will sound in their distinct alarm patterns.

3. Reset the smoke detectors by removing power to the

detectors.

Note: For two wire smoke detectors, use the ESL 405-01 or

405-03 polarity reversal relay module.

ESL 405-05

Polarity Reversal Relay

Burglar / Fire

Alarm Control

Alarm

Output


+

White/Black

White/Red

White

Red

Black

ESL 400 Series Smoke

Detectors

with Sounders

End of
Line Device

ESL 204-12/24V

Power Supervision Relay

Power

Supply

Alarm

Loop

+

+

+

Gray

405-05

Polarity Reversal Relay Module

For use with 4-Wire Sounder Smoke Detectors and

Fire/Burglar Alarm Control Panels

Warning

This polarity reversal device may not be compatible with all

power supervision relays. When using ESL 405 Series

polarity reversal relays on four wire circuits, use the ESL

204 Series power supervision relay at the end of line. Note:

Another option is to use an ESL 449CTE (or CSTE with

Sounder) which incorporates an End-of-Line/Sensitivity

Status Relay Output.

This polarity reversal device cannot be connected to any

coded annunciator.

Typical 405-05 Mounting Locations
in the Control Panel

ESL 405-05 Polarity Reversal Relay Module

ESL 405-05 and 405-06

Relay Modules

Installation Instructions