2.4

Cable Options

RS-485 bus runs can daisy-chain together an NXT-4x4 and NXT-Reader on one line. The total cable run distance should
be less than 500 feet from the NXT controller for runs with 4x4s and less than 1,000 feet for Reader-only runs.

NOTE: Cable resistance causes a drop in voltage at the end of long cable runs. Ensure the appropriate power and current
for your device is available at the device at the end of the cable run. Heavier gauge cable reduces this affect.

NOTE: Keri does not recommend hot-plugging a Reader, RIM, or 4x4 into an NXT controller.

Remove power from the controller prior to connecting these devices.

Table 1: Reader and 4x4 Cable Options

Connection Type

Total

Run

Length

Shielded, Stranded,

2 Twisted-Pair

a

a. Keri recommends this cable type for best system performance.

CAT-5

b

b. Keri’s preferred low-cost option. Keri has no suggested vendor for this type of cable.

Shielded, Stranded,

4-Conductor

c

c. Use care when routing this type of cable as it can make the system more susceptible to EMI.

AWG

Suggest

AWG

Suggest

RS-485 bus

from NXT-2D/-4D

to NXT-4x4 only

up to

500 feet

18 - Data plus

4x4 Power

22 - Data only

Belden

8723

unshielded

18 - Data plus

4x4 Power

22 - Data only

Windy City:

414302-S

West Penn: 244

Tappan:

1880AB4M-CM

RS-485 bus

from NXT-2D/-4D

to NXT-4x4

and NXT Readers

up to

500 feet

18 - Data plus

4x4 Power

22 - Data only

Belden

8723

shielded

18 - Data plus

4x4 Power

22 - Data only

Windy City:

414302-S

West Penn: 244

Tappan:

1880AB4M-CM

RS-485 bus

from NXT-2D/-4D

to NXT Readers only

up to

1,000 feet

22 for Data

Belden

8723

shielded

22 for Data

Windy City:

416303-S

West Penn: 241

Tappan:

2280AB4M-CM

Advertising