60 gauge readings

Read the upper scale only. Reverse the tubes when you turn the fan around to test in the

other direction.

Taking Readings from Two Blowers

If one blower can't get adequate Room Pressure, remove the upper panel cover and install a

second blower. To be absolutely sure the upper panel will stay in place during the test,

tape the edges of the upper panel to the door frame using clear box sealing tape or

masking tape. Don't use duct tape.

Adjust one or both speed controls until the Room Pressure is at the pressure requested by

the Retrotec software. Ideally, adjust both blowers so that they are both running at about

the same speed, and producing approximately the same Flow Pressure. Don't have one going

flat out and the other idling. Both blowers must have their restrictor plates off, i.e. both on

Range 22. Go through computer program per usual, but choose the

multi-blower check off.

Read the Flow Pressure from both blowers and enter them into the

software separately. Do not add them! If you do not have 2 flow

pressure gauges in your system, read the bottom blower, then unplug the

clear tube #1 from the bottom blower and plug it into upper blower.

Read the upper blower flow pressure. Don't touch the speed controls

between reading one flow pressure and the other.

Enter the flow pressures one at a time. After entering them, you proceed

as usual.