2000 Fire Door-Fan Manual

updated 2002-05-28

Page 28 of 58

Two blowers for large rooms, (see also section on flex-duct testing)


Use the second control cord for blower #2. Install while the blower is on the ground, and then install the

blower in the panel.
Complete steps 1 to 3 on the previous page first. Then go to step 7.

7. Turn on the power to blower
#1 and #2.

8. Adjust the speed controls to get
the required room pressure. Read

the room pressure for 30 seconds.

9. When the desired room

pressure is achieved, flip the
toggle up to “Flow”. Read the

flow pressure (Flow #1) for 30
seconds.

10. Read the flow pressure (Flow #2)

for 30 seconds. Turn the blower OFF
with the rocker switches and turn

the blowers around to test the other
direction. Go to Step 6.