Functional Test

AC Mode

The UPS delivers power to the loads derived from the utility and maintains proper battery charge. It also
regulates the output voltage to within a narrow range.

On-Battery Mode

The UPS operates on battery when the line voltage or frequency has fallen outside the limits. Local
users are alerted to this mode of operation by visual and audible indicators. The UPS provides power to
the load from the battery and through its inverter and the output voltage and frequency of the UPS are
regulated within a narrow range

1. Switch

On

Press the power switch on the front panel then the status LCD will

light up.


2. Switch

Off

Press again the power switch, the status LCD on the front panel will go off.


3.

Cold Start / Start on Battery:

This UPS can be turned on even when AC is not present.

Press the power switch on the front panel then the status LCD will light up.

ROUTINE MAINTENANCE AND STORAGE

ROUTINE MAINTENANCE

1.

Use dry soft clothes to clean the front panel and plastic parts. Do not use any detergent that
contains alcoholic ingredient.


2.

The expected lifetime of the battery is around 3 years. Improper operation and harsh environment
will reduce the actual lifetime.


3.

Unplug the UPS from power inlet if the UPS will not operate for long period of time.

STORAGE

1.

First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables
connected the UPS to avoid battery drain.


2.

The UPS should be stored in a cool dry location.


3.

Make sure the battery is fully charged before the UPS is stored.


4.

For extended storage in moderate climates, the battery should be charged for 12 hours every 3
months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat
it every 2 months in high temperature locations.

TROUBLE SHOOTING

Problem

Possible Cause

Solution

Batteries are not fully
charged.

Recharge the battery by leaving the UPS
plugged in.

The UPS does
not perform
expected
runtime.

Battery is slightly worn out.

Contact CyberPower Systems at
[email protected]

The on/off switch is
designed to prevent
damage by rapidly turning it
off and on.

Turn the UPS off. Wait 10 seconds and
then turn the UPS on.

The unit is not connected to
an AC outlet.

The unit must be connected to a
220-240V 50/60Hz outlet.

The battery is worn out.

Contact CyberPower Systems at
[email protected]

The UPS will not
turn on.

Mechanical problem.

Contact CyberPower Systems at
[email protected]

Circuit breaker is tripped
due to overload

Turn the UPS off and unplug at least one
piece connected equipment. Unplug the
power cord of the UPS then press the
circuit breaker knob.

Batteries are discharged

Allow the unit to recharge for at least 4
hours.

Outlets do not
provide power to
equipment

Unit has been damaged by
a surge or spike.

Contact CyberPower Systems at
[email protected]

The serial/USB cable is not
connected.

Connect the serial/USB cable to the UPS
unit and an open serial port on the back
of the computer. You must use the cable
that came with the unit.

The serial/USB cable is
connected to the wrong
port.

Try another serial/USB port of your
computer.

The unit is not providing
battery power.

Shutdown your computer and turn the
UPS off. Wait 10 seconds and turn the
UPS back on. This should reset the unit.

PowerPanel®
Personal Edition
is inactive (all
icons are gray).

The serial cable is not the
cable that was provided with
the unit.

You must use the cable included with the
unit for the software.

CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in

design, assembly, materials and workmanship for two years ( battery is only one year) from the date of

original purchase. Any warranty services, please contact your local dealers or distributors.

TECHNICAL SPECIFICATIONS

Model

Value 1200E

Value 1500E

Value 2200E

Capacity (VA)

1200VA

1500VA

2200VA

Capacity (Watts)

720W

900W

1320W

Input

Input Voltage Range

160VAC~270VAC

Frequency Range

50/60Hz +/-3Hz(Auto Sensing)

Output

On Battery Output
Voltage

Simulated Sine Wave at 230Vac +/-7%

On Battery Output
Frequency

50/60 Hz

Overload Protection

On Utility: Circuit Breaker, On Battery: Internal Current Limiting

Physical

Total # of UPS
Receptacles

(6) IEC 320 C13

Maximum Dimensions

32.6cm(L)

×

14.cm(W)

×

18cm(H)

Weight

13.0 kg / 28.6 Lbs

14.3 kg / 31.5 Lbs

15.4 kg / 33.9 Lbs

Battery

Sealed Maintenance
Free Lead Acid Battery

12V / 7Ah x2

12V / 8.5Ah x2

12V / 9Ah x2

Typical Recharge Time

8 Hours

Warning Diagnostics
Indicators

Power On, UPS Status Display, Capacity Display, Digital Value

Display

Audible Alarms

On Battery, Low Battery, Overload

Environmental

Operating Temperature

+32

°F to 104°F ( 0°C to 40°C )

Operating Relative
Humidity

0 to 95% NON-CONDENSING

Communication

PowerPanel

®

Personal

Edition Software

Windows 98/ME/2000/NT/XP/Vista

Management

Auto-Charger Yes
Auto-Restart Yes
USB Yes


DEFINITIONS FOR ILLUMINATED LCD INDICATORS

LCD Indication

Line mode

UPS Status Display

Capacity Display

Digital Value Display

Select SW

Press

Load
Cap.

Battery

Cap.

Input

Voltage

Output

Voltage

Run

Time

%

of Load

%

of Batt.

Initial

V X -- X V

X

V

1st

V X -- X V

X

V

2nd

V X -- X V

X

V

3rd

V X -- X X

V

V

4th

V X -- X V

X

V

5th(Return)

V X -- X V

X

V

Press >3sec

(Sound Disable)

V

X

V

X

-- -- -- -- -- -- --

Press >3sec

again

(Sound Enable)

V

X

X

X

-- -- -- -- -- -- --

(Overload) V

X

--

V

-- -- -- -- -- -- --

“V” : Illuminated, “X” : Not Illuminated, “--“ : Either

Battery mode

UPS Status Display

Capacity Display

Digital Value Display

Select SW

Press

Load
Cap.

Battery

Cap.

Input

Voltage

Output

Voltage

Run

Time

%

of Load

%

of Batt.

Initial

X V -- X X

V

V

1st

X V -- X X

V

V

2nd

X

V

--

X

V X V

3rd

X V -- X X

V

V

4th

X V -- X X

V

V

5th(Return)

X V -- X X

V

V

Press >3sec

(Sound Disable)

X

V

V

X

-- -- -- -- -- -- --

Press >3sec

again

(Sound Enable)

X

V

X

X

-- -- -- -- -- -- --

(Overload) X

V

--

V

-- -- -- -- -- -- --

“V” : Illuminated, “X” : Not Illuminated, “--“ : Either

For more information, visit eu.cyberpowersystems.com or contact

CyberPower Systems B.V.

Flight Forum 3545 5657DW Eindhoven The Netherlands

Tel: +31 40 2348170, E-MAIL: [email protected]

CyberPower Systems Inc. (USA) 4241 12th Avenue East, Suite 400, Shakopee, MN 55379, U.S.A.

Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: [email protected]

Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole

or in part without permission is prohibited. PowerPanel

®

and PowerPanel

®

Plus are trademarks of

CyberPower Systems (USA) Inc.