Cisco CRS Carrier Routing System 8-Slot Line Card Chassis Site Planning Guide

OL-5802-09

Chapter 3 Technical and Environmental Specifications

Line Card Chassis Specifications

Maximum Power Consumption

(total input power)

Note

Proper grounding is also required at the site to
ensure that equipment is not damaged by
lightning or power surges.

Maximum DC

8.0 kW (assuming 94% efficiency)

Maximum AC

8.5 kW (Delta or Wye 3-phase) (assuming 88%
efficiency)

Power Redundancy (2N)

DC

Three “A” battery plant feeds required for one PDU,
and three “B” battery plant feeds required for the other
PDU.

AC (Delta or Wye 3-phase)

Two independent Delta or Wye 3-phase power sources
required, one for each PDU.

DC Input

Nominal input voltage

–48 VDC North America

–54 VDC Telco (RBOC)

–60 VDC International

(range –40.5 to –75 VDC)

Input current

56 A at –48/–60 VDC (nominal voltage)

66 A at –40.5 VDC (low voltage extreme)

AC Input, Delta 3-phase

3W + PE (3 wire + protective earthing conductor
ground wire)

Input voltage

3-phase 200 to 240 VAC, phase-to-phase (nominal)

(range 170 to 264 VAC, phase-to-phase)

Line frequency

50 to 60 Hz

(range 47 to 63 Hz)

Input current

(PDU rated for 24 A)

30 A

AC Input, Wye 3-phase

3W + N + PE (3 wire + neutral + protective earthing

conductor ground wire)

Input voltage

3-phase 200 to 240 VAC, phase-to-neutral (nominal)

(range 170 to 264 VAC, phase-to-neutral)

(range 295 to 457 VAC, phase-to-phase)

Line frequency

50 to 60 Hz (nominal)

(range 47 to 63 Hz)

Input current

(PDU rated for 14 A)

16 A International

20 A North America

Table 3-1

8-Slot Line Card Chassis Component and Power Specifications—Fixed Configuration
Power (continued)