background image

Charging Ahead

Rogue Engineering Inc.

3860 S. Jason Street

Englewood Colorado 80110

1-800-364-0659 (Toll Free) 1-303-734-0706 (Phone)

1-303-734-0517 (Fax) www.rogue-engr.com

[email protected] or [email protected]

Designed and Manufactured by

Rogue Engineering Inc.

in Englewood, Colorado, U.S.A.

Document Rev. 140305

“Industry Leading Low Self Consumption”

12/24 Volt - 10 Amp SLA

SOLAR BATTERY CHARGE CONTROLLER

Part No. 1950-253

CSA Certifi ed

Class 1 Div 2 Hazardous Locations

Recommended Installation Instructions

DO NOT CONNECT OR DISCONNECT WIRING IN A HAZARDOUS ENVIRONMENT!

1. Securely mount the 1950-253 10A SLA/Flooded Solar Battery Charge Controller

in a certifi ed enclosure near the battery to be charged. The charge controller may

be bolted to a back plate using the available mounting fl anges, or an approved

adhesive may be used to attach the charge controller to an available fl at surface.

2. Run wire from the charge controller’s terminals to the battery. 18 gauge wire is

recommended if the solar panel provides 5 Amps or less charging current, or 12 gauge

wire if it provides more than 5 Amps of charging current. Strip the wire back 3 mm

(~1/8”) and insert the bare portion into the terminal, then tighten the screw until it

crimps down securely on the wire. An approved in-line fuse holder should be wired

in series between +BAT terminal of the charge controller and the positive terminal of

the battery. A 10 Amp fast-blow style fuse is recommended for circuit protection. If

the battery terminals are connected backwards the LED on the charge controller will

light indicating reversed wiring, and the charge controller will not charge the battery.

3. Run cable from the solar panel through the bottom of the enclosure or provided cable

entrance to the +IN and GND terminals on the charge controller. Strip the wire back 3

mm (~1/8”) and insert the bare portion into the terminal, then tighten the screw until

it crimps down securely on the wire. If the battery enclosure is located in a potentially

hazardous area, ensure the use of conduit or approved cable, and properly seal all

wiring entrances as required

.