Chromalox PF207 User Manual

Chromalox, Installation, operation, Hds-1 power disconnect switch kit

Advertising
background image

© 2010 Chromalox

®

, Inc.

Specifications — Table A

* Note: 208V amperage is 86% of 240V value.
† These models can be field changed from single phase to three phase or three phase

to single phase.

Chromalox

®

DIVISION

4

SECTION

SALES

REFERENCE

DATE

SERVICE REFERENCE

PF207

161-305681-001

SEPTEMBER, 2005

(Supersedes PF477-1)

Installation, Operation

and

RENEWAL PARTS IDENTIFICATION

HDS-1 Power Disconnect Switch Kit

for Field Installation in an HVH Series Air Heater

Electrical Data (60 Hz)

Standard

Contactor

Model

Volts

Watts

Phase

Amps

Rating (Qty.)

HVH-02-81

208

2,667

1

12.8

HVH-02-21

208/240

2000/2,667

1

11.1*

——

HVH-02-71

277

2,667

1

9.6

HVH-04-81†

208

4,000

1

19.2

——

HVH-04-83†

3

11.2

30A (1)

HVH-04-21†

208/240

3,000/4,000

1

16.7*

——

HVH-04-23†

3

9.6*

30A (1)

HVH-04-71

277

4,000

1

14.5

——

HVH-04-43

480

4,000

3

4.8

30A (1)

HVH-05-81†

208

5,000

1

24.0

——

HVH-05-83†

3

13.8

30A (1)

HVH-05-21†

208/240

3,750/5,000

1

20.8*

——

HVH-05-23†

3

12.1*

30A (1)

HVH-05-71

277

5,000

1

18.2

——

HVH-05-43

480

5,000

3

6.0

30A (1)

HVH-07-81†

208

7,500

1

36.1

50A (1)

HVH-07-83

3

20.9

30A (1)

HVH-07-21†

208/240

5,625/7,500

1

31.1*

30A (1)

HVH-07-23

3

18.1*

30A (1)

HVH-07-71

277

7,500

1

27.2

30A (1)

HVH-07-43

480

7,500

3

9.0

30A (1)

HVH-10-81†

208

10,000

1

48.0

50A (1)

HVH-10-83

3

27.8

30A (1)

HVH-10-21†

208/240

7,500/10,000

1

41.7*

30A (1)

HVH-10-23

3

24.0*

30A (1)

HVH-10-43

480

10,000

3

12.0

30A (1)

HVH-12-83

208

12,500

3

34.8

50A (1)

HVH-12-23

208/240

9,375/12,500

3

30.1*

50A (1)

HVH-12-43

480

12,500

3

15.1

30A (1)

HVH-15-83

208

15,000

3

41.8

50A (1)

HVH-15-23

208/240

11,250/13,000

3

36.2*

50A (1)

HVH-15-43

480

15,000

3

18.1

30A (1)

This instruction sheet provides information for field installing an
HDS-1 Power Disconnect Switch in an HVH Series air heater.

ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do
so could result in personal injury or property dam-
age. Power Disconnect Switch must be installed by
a qualified person in accordance with the National
Electrical Code, NFPA 70.

GENERAL

Advertising