TriangleTube Prestige Trimax Solo Series User Manual

Prestige trimax boiler manual addendum

Advertising
background image

1

Prestige TriMax Boiler

Manual Addendum

SECTION V - Installing Vent / Com-

bustion Air & Condensate Drain

Installing Vent and Combustion Air

The PRESTIGE must be vented and sup-

plied with combustion air as shown in the

PRESTIGE Vent Supplement, included in

the boiler installation envelope. Refer to

optional vent kit instructions for additional

vent installation instructions. Once instal-

lation is completed, inspect the vent and

combustion air system thoroughly to en-

sure systems are airtight and comply with

the instructions given in the venting sup-

plement and are within all requirements of

applicable codes. Failure to comply with

the installation requirements on the vent-

ing and combustion air piping will cause

severe personal injury or death.

Installing Condensate Drain Assembly
1. Locate the condensate drain assembly and

install as shown in Fig. 14.

2. A metal washer must be installed when in-

stalling the condensate drain assembly. On

all models except the Solo 399, the metal

washer must first be cut using a pair of di-

agonal cutting pliers to make it into a split

washer. Insert the metal washer into the re-

taining nut and screw onto the condensate

drain assembly without rubber gaskets. Use

the condensate drain assembly as a tool to

press the retaining nut with metal washer

onto the polypropylene condensate pan. Un-

screw the condensate drain assembly and

proceed to the next step.

Ensure installation of the condensate drain

assembly included the metal washer. Fail-

ure to comply could result in the trap as-

sembly dislocating from the boiler.

The installer may want to fill the conden-

sate trap with water prior to assembling

on the unit.

3. Slide the rubber seals from the condensate

drain assembly over the heat exchanger con-

densate drain nipple. Connect the condensate

drain assembly to the retaining nut and tighten.

Ensure the condensate drain assembly

contains the plastic seated ball. Do not in-

stall the condensate drain assembly if the

ball is lost or missing, replace the entire

assembly.

4. Remove the compression nut and rubber

seal from the drain outlet.

5. Using 3/4” x 2’ flexible PVC tube provided,

slide the compression nut and rubber seal

over the pipe

The use of 3/4” PVC or CPVC pipe is also

acceptable. If 3/4” pipe is used deburr

and chamfer pipe to allow mating onto

the drain assembly.

6. Thread the rubber seal into the compression

nut to ease installation of the pipe to the

drain assembly.

7. Seat the pipe onto the drain assembly and

tighten the compression nut. Hand tight

only!

The installer may opt to using 13/16" ID

tubing in lieu of rigid piping.

NOTICE

DANGER

WARNING

NOTICE

WARNING

NOTICE

This addendum replaces Section V in the Prestige Installation and Maintenance

Manual

Advertising