FAN

NESTED INLET VANES

EXTERNAL INLET VANES

SIZE

CL 1

CL 2

CL 3

CL 4

CL 1

CL2

CL 3

CL 4

122

N/A

N/A

N/A

N/A

100

100

100

100

135

N/A

N/A

N/A

N/A

100

100

100

110

150

N/A

N/A

N/A

N/A

100

100

100

140

165

100

100

100

130

100

100

130

170

182

100

100

120

160

100

100

150

210

200

100

100

140

190

100

110

180

250

222

100

110

180

240

100

140

230

300

245

100

130

210

290

100

170

280

370

270

100

160

260

350

130

210

340

450

300

120

200

320

430

160

260

410

550

330

150

240

390

520

190

310

500

670

365

180

300

480

640

230

380

610

820

402

220

360

580

770

280

460

750

1000

445

260

440

710

950

340

570

910

1220

490

320

530

860

1150

410

690

1110

1480

542

390

650

1050

1400

510

840

1780

2380

600

480

800

1280

1720

820

1360

2180

2920

660

580

970

1550

2080

990

1640

2640

3530

730

710

1190

2290

3060

1210

2010

3230

4320

807

1050

1750

2800

3750

N/A

N/A

N/A

N/A

890

1280

2120

3410

4550

N/A

N/A

N/A

N/A

982

1550

2590

4150

5550

N/A

N/A

N/A

N/A

SWSI BC/BAF Torque Requirements (in-lb)

DWDI BC/BAF

Torque Requirements (in-lb)

BCS Torque Requirements (in-lb)

FAN

NESTED INLET VANES EXTERNAL INLET VANES

SIZE

CL 17

CL 23

CL 26

CL 17

CL 23

CL 26

270

310

520

730

400

670

940

300

380

640

900

500

830

1160

330

460

780

1090

600

1000

1400

365

570

950

1330

730

1230

1720

402

690

1160

1620

890

1490

2740

445

840

1420

1980

1090

2400

3350

490

1020

1720

2400

1320

2910

4070

542

1260

2100

3540

2130

3570

4990

600

1540

3100

4330

2610

4370

6100

660

1860

3750

5240

3150

5280

7380

730

2740

4590

6410

3860

6460

9030

807

3350

5610

7840

N/A

N/A

N/A

890

4070

6820

9530

N/A

N/A

N/A

982

4960

8310

N/A

N/A

N/A

FAN

NESTED INLET VANES

SIZE

CL 1

CL 2

CL 3

CL 4

165

100

120

200

260

182

100

140

240

320

200

100

180

280

380

222

140

220

360

480

245

160

260

420

580

270

200

320

520

700

300

240

400

640

860

330

300

480

780

1040

365

360

600

960

1280

402

440

720

1160

1540

445

520

880

1420

1900

490

640

1060

1720

2300

542

780

1300

2100

2800

600

960

1600

2560

3440

660

1160

1940

3100

4160

730

1420

2380

4580

6120

807

2100

3500

5600

7500

890

2560

4240

6820

9100

982

3100

5180

8300

NOTES:
1. Standard length of the handle supplied

by Twin City Fan is 10". The force

required to operate inlet vane is:

Torque in In-Lb

Length of Lever

2. For sizing actuator, multiply above

torque by 1.2 for rotary and 1.5 for lin-

ear actuators.

ES-495