Contec 4(FIT)GY 1 User Manual

Specification features packing list, Dio-4/4(fit)gy, F&eit series isolated digital i/o module

Advertising
background image

Ver.1.00

DIO-4/4(FIT)GY

1

F&eIT Series
Isolated Digital I/O Module

DIO-4/4(FIT)GY

*

Specifications, color and design of the products are subject to

change without notice.

This product is an expansion module (device module) that adds
digital signal I/O interfaces to one of various types of controllers.
The product is used in combination with the I/O controller
module <CPU-CAxx(FIT)GY> (*1) or microcontroller unit
<CPU-SBxx(FIT)GY> (*1) in the F&eIT Series.
This product can perform a maximum of 4 points of
Optocoupler isolated input and 4 points of Optocoupler isolated
output per module. (Input: 12 - 24 VDC specified, output: 12 -
48 VDC specified)

*1 This module is available in different product models. "x" in each model number

represents a blank or one alphanumeric character. This is applicable to the rest of this
document.

This product can perform 4-point digital signal input and 4-point
digital signal output, treating 4 points as a group.

Input section is ready to accept both the current sinking output
and current source output.

The output section is a high sink current, open collector type
using high-capacitance transistors.
150 mA/24 VDC or 50 mA/48 VDC max. (per channel)

Isolated I/O operations using an optocoupler improves noise
immunity.

A rotary switch allows you to set device IDs, making it easy to
keep track of device numbers.

Like other F&eIT series products, the module has a 35mm DIN
rail mounting mechanism as standard. A connection to a
controller module can be effected on a lateral, stack basis in a
unique configuration, which permits a simple, smart system
configuration without the need for a backplane board.

Module[DIO-4/4(FIT)GY] …1
First step guide … 1
CD-ROM [F&eIT Series Setup Disk] *1…1
Interface connector plug…1

*1 The CD-ROM contains various software and User’s Guide.

Specifications

Specifications

Item

DIO-4/4(FIT)GY

Input section

Input format

Optocoupler isolated input
(compatible with current sink output and current source
output)

Input resistance

3k

Ω

Input ON current

3.4mA or more

Input OFF current

0.16mA or less

Number of input signal points 4 points (4 points/common)
Response time

Within 1msec

External circuit power supply

12 - 24VDC (±15%)
(4mA/12V - 8mA/24V per channel)

Output section

Output format

Optocoupler isolated open collector output (current sink type)

Output voltage

12 - 48VDC (±15%)

Ratings

Output current

150mA (12 - 24V) (per channel) (Max.)
50mA (36 - 48V) (per channel) (Max.)

Number of output signal
points

4 points (4 points/common)

Response time

Within 1msec

External circuit power supply

12 - 48VDC (±15%)

Common section

Interrupt level

Using CPU-SBxx(FIT)GY: IRQ 5, 7, or 9

Internal current consumption

5VDC(±5%) 150mA(Max.) *1

Allowable distance of signal
extension

Approx. 50m (depending on wiring environment)

Physical dimensions (mm)

25.2(W) x 64.7(D) x 94.0(H) (exclusive of protrusions)

Weight of the module itself

100g

Module connection method

Stack connection by means of a connection mechanism
standard with the system.

Module installation method

One-touch connection to 35mm DIN rails
(standard connection mechanism provided in the system)

Applicable wire

AWG 28 - 16 wire type: 0.32 - 1.30mm

Applicable plug

FRONT-MC 1,5/12-STF-3,81 (made by Phoenix Contact
Corp.)
3.81mm-pitch, rated current: 8A (Max.)

*1 The stack connector accepts currents of up to 3.0A (Max.).

Installation Environment Requirements

Item Requirement

description

Operating temperature

0 - 50

°C

Storage temperature

-10 - 60

°C

Operating humidity

10 - 90%RH (No condensation)

Floating dust particles

Not to be excessive

Corrosive gases

None

Line-noise
*1

AC line/2kV, Signal line/1kV
(IEC1000-4-4Level 3, EN61000-4-4Level 3)

Noise immunity

Static
electricity
resistance

Contact discharge/4kV (IEC1000-4-2Level 2,
EN61000-4-2Level 2)
Atmospheric discharge/8kV (IEC1000-4-2Level 3,
EN61000-4-2Level 3)

Vibration
resistance

Sweep
resistance

10 - 57Hz/semi-amplitude 0.15mm, 57 - 150Hz/2.0G
80minutes each in X, Y, and Z directions
(JIS C0040-compliant, IEC68-2-6-compliant)

Impact resistance

15G half-sine shock for 11ms in X, Y, and Z directions
(JIS C0041-compliant, IEC68-2-27-compliant)

*1 When using a POW-AD22GY

Specification