coil clean, reducing maintenance costs. Also, air
coming from the coil will frequently be near

100% relative humidity.

3. The air flow temperature thru the air cleaner

must be within 40 F to 125 F.

Location

— Because air-handling systems vary

greatly in arrangement and style, factors such as
accessibility, ambient temperature ratings, tran­
sitions, and other requirements must be carefully
considered.

In crawl space or attic installations (uncondi­

tioned space), air cleaner must be insulated the
same as ductwork.

The unit must be readily accessible for periodic

inspection and cleaning of the prefilter and elec­

tronic cells to maintain maximum efficiency and
trouble-free operation. A minimum of 30 in. of
clear area should be left in front of the air cleaner
for cell and prefilter removal.

The air cleaner must be installed where the

temperature will be within a 40 F to 125 F range.

Humidifiers

— Location of the system humidifier is

important to the operation of the electronic air
cleaner or mechanical filter.

When an evaporative-type humidifier is used, it

may be installed between the furnace warm air
duct and the return air duct without affecting the
electronic air cleaner.

An atomizing-type humidifier must be installed

downstream from the air cleaner. If the atomizing-
type

humidifier

is

installed

upstream,

high

humidity, salts and minerals will decrease the

efficiency of the electronic cell and cause service
problems or damage the high-efficiency filter
element in the mechanical air filter.

Outdoor Air

— When outdoor air is added to the

return air duct, sufficient heat must be added to
maintain the return air temperature at 40 F mini­

mum. Lower temperatures can cause ionizer wire
failure under certain conditions. Two methods are
recommended:

1. Mixing baffles or vanes. When outdoor air is

added, make certain that it is far enough ahead
of the air cleaner to be mixed and warmed

properly. If not, baffles must be installed to

force mixing of the air.

2. Preheat coil. If a large amount of outdoor air is

used, it must be heated. A thermostat should be
used to control the heater. (A strip heater or
hot water coil are typical heaters.)

INSTALLATION PROCEDURE

Remove Filter and Clean Blower Compartment
Before Starting Installation.

1. Remove and discard the old filter if one is used.

2. Thoroughly clean the blower compartment.

The air cleaner cannot remove (firt from the
blower compartment or distribution ducts.

Installation of 31MP Plate-Type or SIMM Media-

Type Air Cleaner

1. Remove power door by turning fastener knob.

Fig. 2, item 5, counterclockwise until power
door is free. Slide out prefilter and air cleaner
cells.

1

— Cabinet

2 - Collector Cell (31 MP)
3 — Prefilter
4 — Power Door
5 — Fastener Knob
6 — Test Button

7 — Indicator Light
8 - ON-OFF Switch
9 — Ceramic Insulators

10 — Opening for Power Supply
11

— Junction Box Cover

Fig. 2 — Electronic Air Cleaner Components,

Model 31 MP

2. Unit can be installed with air flow thru the

cabinet in either direction. No changes to the
cabinet are necessary when reversing the air
flow direction thru air cleaner. See Fig. 3.

3. Apply template, supplied in package, to side of

furnace and prepare the opening in side of
furnace according to instructions on template.

4. Prepare return air duct for installation of unit.

Allow a minimum of 30-in. clearance in front

of power door for servicing.

5. Return air duct should use full cabinet open­

ing. Run duct straight into unit. Use an elbow
with turning vanes if duct takes a sharp turn
close to air cleaner inlet. Do not baffle off any

portion of entering air side of air cleaner

When it is necessary to change duct size close
to the air cleaner, use gradual transitions to
reduce turbulence. See Fig. 4.