Carrier 50EQ User Manual

Single-package heat pumps

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Number One
AirConditbning
l\Mer

Division of
Carrier Corporation

Carrier Parkway • Syracuse, N Y 13221

Single-Package Heat Pumps

INSTALLATION

Rigging and Unit Placement

— Inspect unit for

transportation damage. File claim with transporta­
tion agency. Do not drop unit. Keep unit upright.

Units are designed to be hoisted only. However,

units with optional shipping skids may be moved
with a fork truck. Use spreader bars over unit to
prevent sling or cable damage to unit. Level unit by

using unit frame as reference. Leveling tolerance is
± 1 /16 in. per linear ft in any direction. See Fig. 1 for
additional information. Unit weight is shown in

Table 1.

Roof Curb

— Assemble and install accessory roof

curb in accordance with instructions shipped with

accessory. (In areas of prolonged sub-freezing tem­
peratures or heavy snowfall, the use of an 18-in.
high roof curb is recommended. This permits proper
drainage during defrost.) Refer to Fig. 2.

Install insulation, cant strips, roofing and flashing

as required. Ductwork can be installed to roof curb

«OTES;

t, A!i BTift (lanets jnust be in piece when rtg8^ns

2. Oo not bandte unit wsdi 'torit iruciis.

3. Use4«ei)}esan«i4"24>y-4Vor "4-by-4V'of ctenenaons

shown.

© Carrier Corporation 1979

Fig. 1 — Rigging Details

before unit is set in place. Curb should be level. Unit
leveling tolerance is ±1/16 in. per linear ft in any
direction. This is necessary to permit unit drain to
function properly.

Cut hole(s) in roof to accommodate return and

supply ducts only. Refer to accessory installation

instructions.

Roof Mount

— Check building codes for weight

distribution requirements.

Alternate Unit Support Methods

— Where the

preferred curb or slab mount cannot be used, sup­
port unit with sleepers along unit perimeter using
unit curb-support areas. However, if sleepers cannot
be used, support long sides of unit (dimension “A,”
Fig. 3) by three 4-in. by 4-in. pads, equally spaced.

Units may sag if supported by corners only.

Positioning

— Position unit so that drifting snow

does not build up on outdoor coil. Provide clear­
ances around and above the unit for airflow, safety,

and service access (Fig. 3).

Do not install unit in an indoor location. Do not

locate unit air inlets near exhaust vents or other
sources of contaminated air.

Although unit is weatherproof, guard against

water from higher runoff and overhangs.

Field-Fabricated Ductwork

— Secure all ducts to

building structure. Use flexible duct connectors be­

tween unit and ducts as required. Insulate and
weatherproof all external ductwork, joints and all

roof openings with flashing and mastic in accord­
ance with applicable codes.

Ducts passing thru unconditioned spaces must be

insulated and covered with a vapor barrier.

Unit Duct Connections

— Ductwork openings

are shown in Fig. 3.

Economizer Hood Installation, Fig. 4

— The

economizer mechanism and allelectrical connections
are factory installed and adjusted. The hood assem­
bly, outdoor air inlet screens and required hardware
are shipped separately and must be field installed.

NOTE: There is a linkage rod and 3 fasteners (speed
nuts) shipped with the economizer hood assembly.
This rod is not required on 50EQ units.

Install economizer hood(s) as follows:

1. Loosen unit top panel sheet metal screws above

outdoor air inlet opening.

2. Assemble hood top panel, side panels and

support channel.

Form 50EQ-4SI

Advertising