Table 12 — Refrigerant Piping Sizes

(Double Suction Riser)

LGTH OF INTERCONNECTING PIPING

CONDENSING

26-50

51-75

76-100

UNIT

L ine Size ( n. OD)

A

B

C

A

B

C

A

B

C

38AD034

_

_

_

_

_

2%

l=/8 2 Vs

38AE044

-

2%

1%

2%

2\

1%

2 Vs

38AE054

2Vs

2%

2%

1%

2%

2\

2%

2 Vs

NOTE: Double Suction Risers are sized according to the equal area
method and are based on standard unloading available

Table 13 — Liquid Line Data

MAXIMUM

FILTER-DRIER

AND

SIGHT GLASS

CONN. SIZES

(in. flare)

CONDENSING

UNIT

ALLOWABLE

LIQUID

LIFT (ft)

38GR006

90

Vs

38BA008

60

Vs

38BA009

45

V

38AD012

71

Vs

38AD014

46

Vs

38AD016

70

Vs

38AD024

84

Vs

38AD028

64

5/

5

® See Note 2

/a

38AD034

46

38AE044

73

38AE054

38

See Note 3

38AE064

56

NOTES

1 Maximum allowable liquid lift is based on 7 psi pressure

drop for accessories and a 2 F liquid line loss

2

Units 38AD028 and 034 have 2 filter-driers and one sight

glass All other units have one of each

3 Filter-driers and sight glasses are factory supplied except

for the 38AE units Connections are for both ends

CONDENSING

UNIT

@

— Suction riser

with

trap

©

— Suction line to condensing unit

Fig. 2 — Suction Line Piping

Liquid line solenoid valve serves 2 coils

Fig. 3 — Location of One Liquid Line

Solenoid Valve Serving 2 Coils

15