Carrier 38BA User Manual

Page 19

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 16 — Electrical Data — 40RR

UNIT
40RR

NOMINAL

VOLTAGE

SUPPLIED
VOLTAGE

RANGE*

FLA

MWA

200-230

■¡8Q-264

9.6-8:8::i

008

200

180-229

3 9

4 9

230/460

207-264/414-528

3.8/1.9

4 8/2.4

012

200

180-229

7 1

8 9

230/460

207-264/414-528

6 2/3 1

7 8/3 9

016

200

180-229

7.1

8.9

230/460

207-264/414-528

6 2/3 1

7 8/3 9

024

200

180-229

10 6

13.2

230/460

207-264/414-528

9 2/4 6

1 1 5 / 5 8

■ Single-phase; all others are 3-phase

FLA

— Full Load Amps

MWA

— Minimum Wire Amps Complies with National Elec­

trical Code

*Units are suitable for use on electrical systems where voltage

supplied to the unit terminals is not below or above the listed
range limits

NOTE: Fan motors are not supplied with 40RR028 — 054 units

Table 17 — 40BA Accessory Electric Heat

HEATER

PKG NO.

40BA

ELECTRICAL

CHARACTERISTICS

KW

FULL
LOAD
AMPS

MIN

WIRE
AMPS

900041

230-1-60

9 0

39 2

49 0

900081

230-3-60

9 0

22 6

28 3

900091

460-3-60

9 0

11 3

14 1

CR

— Control Relay

HD

— Fleating Device

IFC

— Indoor Fan Contactor

IFR

— Indoor Fan Relay

LLS

- Liqu id Line Solenoid

R

— Relay

TRANS

— Transformer

[3

Terminal Block

Conn

For multiple 38AD.AE condensing units with a single air

handler, disconnect contactor CR2 from terminal no Sand

insert a field-supplied relay between contactor CR2 and
terminal no 7 This field-supplied relay energizes the second

condensing unit, at terminal no 1 and terminal no 2

Liquid line solenoid valves

38AD016—024 — Omit LLSV2 Omit LLSV1 (Foronestep

cooling and when using multiple condensing units with a

single fan coil )

38AD024—034 — Omit LLSV2 for one step cooling When

using

multiple

condensing

units,

remove

LLSV2

from

condensing unit no 1 and connect it between terminal no 5

and no 7 on condensing unit no 2 terminal block

38AE044—064 — LLSV1 only is required on 2 step cooling

system with less than 125 ft of interconnecting piping No

LLSV required on one step cooling with less than’ 125 ft of

interconnecting

piping

If

using

more

than

125

ft

of

interconnecting piping and multiple condensing units, refer

to instructions above for 38AD024—034

> Fig. 6 — 38AD, AE Control Circuit Field Wiring

for 110 V Control Circuit Voltage

19