Find heating capacity of selected fan-coil unit, Iv determine fan rpm and bhp, V determine size of liquid and suction lines – Carrier 38BA User Manual

Page 2: Vi find size nozzle, txv and solenoid valve

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

64 F evaporator entering air wb temperature,

the system has a total capacity (TC) of 600,800
Btuh, and a calculated sensible heat capacity
(SHC) of 498,800 Btuh. For close-coupled
systems (15 ft or less of interconnecting pipe),
an additional 2% may be added to both TC and
SHC. As this system is not close-coupled, the
ratings are used directly from the combination
ratings. At this point, the sensible heat capacity
is adjusted for the evaporator entering air db
temperature. For 20,000 cfm, the bypass factor
is 0.18. The adjusted sensible heat capacity is:

Adj SHC = SHC

+

[1.09 X cfm x (1—bf)

X (edb-80)]

= 498,800 + [1.09 X 20,000

X

(1-.18)

X

(77-80)]

= 498,800- 53,600
= 445,200 Btuh

Therefore, the selected system will meet all

cooling requirements.

Find heating capacity of selected fan-coil unit.

Enter Table 3, page 10, for 40RR054 and
20,000 cfm. A one-row nonfreeze steam coil
will deliver 915,000 Btuh based on 60 F enter­
ing air temp, and 2 psig steam. To find the
corrected heating capacity, enter Table 1, page

10, for steam coils at 5 psig steam and 58 F

entering air temperature. By interpolation, the
correction factor is 1.062.

Corrected capacity =

Leaving air db

915,000 X 1.062
971,700 Btuh

corrected capacity

1.09 X cfm

edb -t-

58 +

97\_J00

1.09 X 20,000

= 102.6 F

The heating coil has sufficient capacity and the
leaving air db is less than the maximum

temperature of 140 F.

IV Determine fan rpm and bhp.

Refer to Table 14, page 17, for a 40RR054 at
20,000 cfm and 1.12 in. wg external static

pressure, plus 0.07 in. wg for the heating coil

(Table 4), indicates a fan rpm of 828 and
requires 12.6 bhp. As this rating point is within

the shaded area, the fan drive must be selected
and purchased locally.

V Determine size of liquid and suction lines.

Table 11, page 14, indicates the pipe sizes for
the various condensing units. These sizes are
based on an equivalent length equal to the
maximum length indicated plus 50% for fit­
tings. A more accurate estimate may result in
smaller pipe sizes. Enter the table with the
condensing unit (38AD024) and the estimated
length of interconnecting pipe (90 ft). The
suction line will be 2 1/8-in. OD and the liquid
line is 7/8-in. OD. Similarly, for the 38AD016,
the suction line is 2 1/8-in. OD and the liquid
line is 7/8-in. OD. If a 38AD034 — 38AE054
condensing unit is used with more than 25 ft of
piping, a double suction riser may be required.

VI Find size nozzle, TXV and solenoid valve.

To determine the nozzle(s), TXV(s), and sole­
noid valve(s), enter Table 6, page 13, with the

system number. Tables 7, 8, 9, and 10 give the
part numbers for the keys indicated in the
previous table. For this example, a C12 nozzle
would be used in each of the 3 distributors.
Also, the TXV’s and solenoid valves used would
be (using Carrier Part No.):

FAN

COIL

40RR054

COND

UNIT

38AD024

38AD024

38AD016

COIL
SECT

u

M

L

TXV

EA03PC503

SOLENOID

VALVE

EF11BS28

EE11BS28

None Requ ired

Part numbers for Alco and Sporlan valves are
obtained in a similar fashion. Also, for several
systems, a single solenoid valve will control
both the middle and lower coil sections as
exemplified by system no. 49. These systems
should be piped in accordance with Fig. 5, page

16. When the condensing unit is below the

fan-coil unit, the maximum liquid lift as pre­
sented in Table 13, page 15, should be adhered
to.

Advertising
This manual is related to the following products: