Table 18 — Minimum Outdoor Operating Temperature

%

MIN OUTDOOR OPER

UNIT

NO. OF

FULL

TEMP (F)

CYL

LOAD

Standard

With Head

CAP.

Unit

Press. Control*

38GR006

4

100

45

-20

38BA008

4

100

55

-20

38BA009

6

100

50

-20

38AD012

6

100

20

and

4

67

34

-20

38AD014

2

t

33

47

38AD016

6

4

100

67

0

20

-20

38AD024

4

2

100

50

0

20

-20

38AD028

6

100

15

and

4

67

30

-20

38AD034

2

33

45

8

100

38

38AE044

6

4

75
50

41

44

-20

2

25

57

10

r 100

14

8

80

29

38AE054

6

60

34

-20

4

40

40

2

20

47

12

100

14

10

83

17

38AE064

8

6

67
50

24t

32

-20

4

33

45

2

17

58t

*Accessory 32 Series Motormaster®Control

i Requires accessory pressure-operated unloader package

NOTE: Minimum outdoor air operating temperatures are based
on the following conditions:

MIN COND TEMP

90 F

80 F

%

COMPR CAP.

100-75

75-50

70 F

50-17

On applications with multiple DX coils, the compressor may be
unloaded while an individual zone coil (s) is still fully loaded For
proper expansion valve operation under this condition, maintain
a 90 F condensing temperature Increase allowable minimum
outdoor operating temperature by the difference (F) between
required 90 F condensing temperature, and the minimum con­
densing temperature shown in footnote table with compressor
unloaded A 90 F condensing temperature may be maintained by
using

the

Motormaster

control

'regardless

of

outdoor

air

temperatures down to —20 F

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Tab 4

Form 38AD-5XA Supersedes 38AD-4XA

Printed in USA

5-75

Codes B and MS

Catalog No 51 3-801