COMBINATION RATINGS

i 38GR006 and 40BA009

Ratings Notes

1. Direct interpolation is permissible. Do not

extrapolate.

2. SHC is based on 80 F db temperature of air

entering evaporator coil.

Below 80 F db, subtract (corr factor x cfm)
from SFIC.

Above

80 F

db, add (corr. factor

x

drn) to

SHC.

ENTERING AIR DRY -BULB TEMP (F)

BYPASS

79

78

77

76^

— r

75 1 under 75

FACTOR

81

85

ovec/85

Correction Factor

.10

97

1.95

2 92

3 89

4.86

use formula

.20

86

1 73

2.59

3 46

4 32

.30

76

...

1 51

2.27

3 03

3 78

shown be low

Interpolation is permissible

Correction Factor = 1 08 x (1

BF) X (db - 80)

3. Gross capacities shown do not include a deduc­

tion for evaporator fan motor heat.

4. Formulas:

hdb “ tedb

sensible heat capacity (Btuh)

1.08 X cfm

tiwb “ wet-bulb temperature corresponding to

enthalpy of air leaving evaporator coil
(hlwb)

hlwb - hewb

total capacity (Btuh)

4.5 X cfm

where hewb ~ enthalpy of air entering evap coil

5. Combination ratings are based on a 2 F line

loss. For a close-coupled system (less than

15 ft),

add 2%

to ratings. Piping sizes in Table

13 are based on 2 F line loss. All combination

ratings are based on R-22.

T emp(F)

Air Ent

2875/. 13

Evgp Air - Cfm/BF

3825/. 16

4775/. 19

Evap Air - Ewb (F)

72

67

62

72

67

62

72

67

62

TC

81

74

69

83

77

74

84

78

77

85 SHC

46

60

69

53

70

74

59

76

77

KW

8.2

7.7

7.4

8.3

7.9

7.7

8.4

8.0

7.9

TC

75

69

65

77

71

69

78

72

72

95 SHC

44

57

65

51

67

69

57

72

72

KW

8.7

8.2

7.9

8.9

8.4

8.3

9.0

8 5

8.5

TC

72

66

63

74

68

67

74

69

70

100 SHC

43

58

63

50

65

67

56

69

70

KW

8.9

8.4

8.2

9.1

8.6

8.5

9.2

8.8

8.8

TC

69

64

61

71

66

65

71

67

67

105 SHC

42

56

61

49

64

65

55

67

67

KW

9.2

8.7

8.4

9.4

8.9

8.8

9.5

9.0

9.0

TC

63

59

57

64

60

60

65

62

62

115 SHC

40

53

57

47

60

60

53

62

62

KW

9 6

9.1

8.9

9.8

9.3

9.3

9.9

9.5

9.6

38BA008 and 40BA009

ARI - 88,000 Btuh

Temp(F)

Air Ent

Evap Air - Cfm/BF

2500/. 16

3400/.23

4300/.28

Evap Air - Ewb (F)

72

67

62

72

67

62

72

67

62

TC

101

93

85

105

97

89

108

99

91

85 SHC

50

62

74

55

70

86

59

70

91

KW

7.7

7.4

7.0

7.8

7.6

7.2

7.9

7.6

7.3

TC

96

89

81

100

92

85

102

94

87

95 SHC

48

60

72

53

68

84

57

75

87

KW

8.4

8.0

7.6

8.5

8.2

7.8

8.6

8,2

7.9

TC

94

86

79

98

89

83

100

91

85

100 SHC

48

59

71

52

68

81

56

74

84

KW

8.7

8.4

7.9

8.9

8.5

8,1

8.9

8.6

8,2

TC

91

84

77

95

87

80

97

89

82

105 SHC

47

58

70

52

67

80

55

73

82

KW

9.1

8.7

8.2

9,3

8.9

8.4

9.4

9.0

8.5

TC

86

79

73

90

82

75

91

84

77

115 SHC

45

57

68

50

65

75

53

71

77

KW

9.8

9.4

9.0

9.9

9.5

9.1

10 1

9.7

9.3

^^38BA009 and 40BA009

AR

- 100,000 Btuh

Evap A ir - Cfm/BF

Air Ent

2500/. 16

3400/.23

4300/.28

Ci

E vap Air - E wb (F)

72

67

62

72

67

62

72

67

62

TC

112

103

94

118

108

99

121

112

102

85 SHC

54

67

79

59

75

90

64

82

101

KW

10.5

9.9

9.5

10.7

10.2

9.7

11,1

10.5

9.9

TC

108

99

90

113

104

95

1 16

107

98

95 SHC

53

65

77

58

73

88

62

80

98

KW

11.2

10.7

10.2

11.6

11,0

10,5

11.9

11,3

10.6

TC

105

96

89

no

101

93

113

104

95

100 SHC

52

64

76

57

72

87

61

79

95

KW

1 1.6

11.1

10.5

12.0

1 1.4

10,8

12.3

11.7

10,9

TC

102

94

86

106

98

90

109

101

92

105 SHC

51

63

75

56

71

86

60

78

92

KW

12.0

11.4

10.8

12.5

11.8

11.0

12.7

12.1

1 1.3

TC

96

89

81

101

92

83

103

95

87

115 SHC

49

61

72

54

69

83

58

76

87

KW

12 8

12 2

1 1 6

13 2

12 5

11 9

13 4

12 7

12 1

38GR006 and 40RR008

LEGEND

E vap Air — Cfm/BF

2525/. 19

3375/.23

42257.26

BF — Bypass Factor

r.

E vap A ir — Ewb (F)

TC — Total Capacity (1000 Btuh)

72

67

62

72

67

62

72

67

62

SHC — Sensible Fleating Capacity (1000 Btuh)

TC

79

71

65

81

74

70

83

76

74

KW >- Compressor Motor Power Input

85 SHC

43

55

65

50

64

70

56

72

74

Ewb — Entering Wet-Bulb

KW

7.7

7,2

6.9

7.9

7,4

7.2

8.0

7.6

7.4

U - Upper Coil

TC

73

67

62

75

69

66

76

71

69

M — Middle Coil

95 SHC

41

54

62

48

62

66

53

69

69

L — Lower Coil

KW

8.2

7.7

7.4

8.1

7.9

7.7

8.5

8.1

7.9

U-M-L abbreviations indicate connection of condensing unit to upper.

TC

71

64

60

73

67

64

74

68

67

middle or lower coil of fan-coil unit

100 SHC

40

53

60

47

61

64

52

67

67

KW

8.4

8.0

7.6

8.6

8.2

7,9

8.7

8.3

8.2

TC

68

62

58

70

64

62

71

66

65

105 SHC

39

52

58

46

60

62

51

65

65

KW

8.7

8.2

7.9

8.9

8.4

8.2

9,0

8.5

8,4

TC

63

58

55

65

60

58

65

61

61

115 SHC

38

50

55

44

57

58

49

61

61

KW

9.1

8.6

8.3

9.3

8.8

8.7

9 4

8.9

8 9