Sears 1F86-382 User Manual

1f86, Foperatoitsave^theselrtsim, Description

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Home Services

1-800-4-MY-HOME

1F86--382

Non-Programmable Electronic Digital Thermostat

INSTALLATION AND

OPERATION INSTRUCTIONS

fOperatoiTSave^theselrTsim

FAILURE TO READ AND FOLLOW ALL

INSTRUCTIONS CAREFULLY

BEFORE

INSTALLING OR OPERATING THIS CONTROL COULD CAUSE

PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

Your new Digital Thermostat uses the technology of a solid-state

microcomputer to provide precise temperature control.

Features:

• Simultaneous heat and cool setpoint storage

• Pre-set temperature control

• Backlit display

• LCD continuously displays setpoint and room temperature

• °F/°C convertibility

Temperature range 45° to 90°F

RC, RH, C, W, Y, G , O and B terminals

Optional C terminal (Dual Power option)

B and O terminals for single stage heat pumps (no auxiliary
heat) or damper operation

Setpoint storage in case of power loss

2 "AA" alkaline batteries included

PRECAUTIONS

This thermostat is intended for use with a low voltage system;
do not use this thermostat with a line voltage system. If in doubt
about whether your wiring is millivolt, line, or low voltage, have

it inspected by a qualified heating and air conditioning contrac­

tor or electrician.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes

and ordinances.

This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could
cause the control to malfunction.

A WARNING

Do not use on circuits exceeding specified voitage.
Higher voitage will damage control and could cause

shock or fire hazard.

Do not short out terminais on gas vaive or primary
controi to test. Short or incorrect wiring will damage

thermostat and could cause personal injury and/or

property damage.

Thermostat instaiiation and all components of the sys­
tem shall conform to Class II circuits per the NEC code.

A

CAUTION

To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.

SPECIFICATIONS

ELECTRICAL DATA

Electrical Rating:

8 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)

THERMAL DATA

Setpoint Temperature Range:

45°F to 90°F (7°C to 32°C)

Operating Ambient Temperature Range:

32°F to 105°F

Operating Humidity Range:

0 to 90% RH (non-condensing)

Shipping Temperature Range:

-4°F to 150°F

APPLICATIONS

For use with:

Standard heat/cool or heat only systems

Electric heat systems

Gas or oil fired systems

Gas systems with intermittent ignition devices (I.I.D.)
and/or vent dampers

Hydronic (hot water or steam) systems

Single-stage heat pump systems (no auxiliary heat)

Millivolt systems

DO NOT USE WITH:

Multi-stage systems

Systems exceeding 30 VAC and 1.5 amps

3-wire zoned hydronic heating systems

PART NO. 37-6925A

0811