Parti the revolving field ac generator – Generac Power Systems 53187 User Manual

Page 33

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

PARTI

THE REVOLVING FIELD AC GENERATOR

1

SECTION 1.6- TROUBLESHOOTING

(UNITS WITH 15 INCH STATOR)

Detailed Instructions

TEST 3- REPLACE REGULATOR, TEST/ADJUST;

Discussion: The Voltage Regulator lam ps (LED’s)

are norm ally ON. If the 'Regulator* lam p is OUT, the
Voltage Regulator has shut dow n or has failed. A
'Regulator

lam p

ON

condition

indicates

the

Regulator’s SCR’s (silicone controlled rectifiers) are
firing.

"U--- " ^ .---------------------------------- — .. - 1 ^

V

VOCTAQE ADJUST

OAIN

In^

STABIUmr

Ine®

UNOERFREOUENCY

ADJUST

r«®

REGULATOR

SENSING

«

EXCITATION

®

Figure 2. The Part No. 67680 Voltage Regulator

Procedure: Unplug the voltage regulator connec­

tor plug. Rem ove the screw s, flatw ashers and

lockw asners that retain the regulator to the control
panel. Rem ove the regulator. Install the new regulator,
test and adjust as outlined in Section 1.9,

‘OPERA­

TIONAL TEST S AND ADJUSTM ENTS'.

NO TE: Before attem pting to adjust the voltage reg­
ulator, the engine governor m ust be properly ad­

justed to m aintain a no-load frequency of 60.5-63.5

Hertz (1815-1905 rpm ). Correct no-load AC output

voltage setting Is 121-127 volts AC (llne-to-neutral),
or 242-257 volts AC (llne-to-llne).

Results: If problem is corrected, discontinue tests.

If problem still exists, continue troubleshooting as indi­

cated in the 'Flow Charts".

TEST 4- TEST EXCITATION CIRCUIT BREAKER:

Discussion: See Figure 3. The excitation circuit

breaker is electrically connected in series w ith the
stator excitation w inding AC output to the voltage reg­
ulator. It is physically m ounted in the control panel

interior. Should the breaker fail open, loss of excitation
w inding output to the regulator w ill occur. W ithout exci­
tation current, the regulator w ill shut dow n and gener­
ator AC output w ill drop to a voltage com m ensurate w ith

Rotor residual m agnetism . The breaker cannot be reset
m anuaily (it is norm ally self-resetting). If it has failed

open, it m ust be replaced.

from excitation grinding

to voltage regulator

Figure 3. Excitation Circuit Breaker

Procedure: To prevent interaction, disconnect

W ires No. 2 and 162 from the circuit breaker term inals.

Set a VOM to its "Rxl' scale and zero the m eter.
Connect thè VOM test probes across the tw o circuit
breaker term inals. The m eter should read "continuity*.

Resuits: •

1. If the m eter displays any reading o(;her than "conti­
nuity", replace the excitation circuit breaker.

2. If the VOM reads "continuity", go on to Test 5.

NO TE: W hen reading resistance across the circuit
breaker contacts, a very sm all resistance reading
Is acceptable. An oxide film can build up on circuit
breaker contact surfaces, causing the sm all resis­

tance.

TEST 5- TEST STATOR EXCITATION W INDING:

Discussion: An open circuit in the stator excitation

(OPE) w inding w ill result in loss of excitation current to

the Voltage Regulator. An excitation w inding AC output
of approxim ately 4-8 volts AC is required to turn the
Voltage Regulator on. Thus, on loss of excitation w ind­

ing output, the Regulator w ill shut dow n and regulated
excitation current to the Rotor w ill term inate. Generator
AC ou^ut voltage w ill then drop to a value com m ensu­
rate w ith Rotor residual m agnetism plus field boost

current (about one-half norm al no-load AC output volt­
age). An open w inding w ill be Indicated by a VOM

reading of 'infinity* or a very high resistance reading. A
shorted excitation w inding w ill be Indicated by a veiy
low resistance reading. In the follow ing 'Procedure*^,

the excitation w inding w ill also be testedfor a grounded
condition.

Procedure: See Figure 4, next page. In the control

panel, locate unattached W ire No. 5. This is the therm al
protector bypass lead. Rem ove the w ire nut from end
of W ire No. 5. Also locate W ire No. 6, connected to Pin
6 of the voltage regulator plug. On som e units, a barrel
lug m ay be used to connect W ire No. 6 betw een the
voltage regulator and the stator excitation w inding. Test
the stator excitation w inding for an open, shorted or
grounded condition as follow s:

PAGE 1.6-5

Advertising