Installation Instructions

OUTDOOR HE ATI N G UNIT

379A

Models

48W- & 60W-379A

Series C

fariiant

Bryant Models 48W-379A and 60W-379A are outdoor

heating units designed for installation on a rooftop or

at ground level. Both models have a chilled water coil

factory installed. Model 48W-379A is equipped with a
48.000 Btuh coil while Model 60W-379A is equipped

with a 60,000 Btuh coil.

These units were designed for use in split systems with
matching Bryant gas-fired water chillers. Both models
have 150,000 Btuh heating input rating and a 112,500
Btuh heating output rating. Model 48W-379A has a

48.000

Btuh cooling rating when connected to a

Bryant Model 48-453 Gas-Fired Water Chiller. Model
60W-379A has 60,000 Btuh cooling rating when con­

nected to a matching Bryant Model 60-452 Gas-Fired
Water Chiller.

Important—Read before Installing

1. Check all local or other applicable codes for in­

formation concerning proximity to property lines,
height above roof, obstructions, etc.
2. Be sure the power supply available (voltage,

frequency, and phase) corresponds to that specified

on the unit rating plate.
3. Check the electrical service provided by the utility

for the building to be sure that the service capacity is
sufficient to handle the load imposed by this unit.
4. Refer to the regulations of the serving gas supplier

and the local building, heating, plumbing, or other
codes in effect in the area in which installation is to
be made.
5. Refer to the dimensional drawing on page 2 for

location of electrical, gas, and chilled water con­
nections prior to setting the unit in place.

GENERAL

The design of this unit is certified by A.G.A. for use
with natural or propane gases with appropriate con­
trols and orifices. This unit is designed for outdoor in­
stallation only.

Installation of the unit consists of the following:

I. Locating the Unit

II. Gas Piping

III. Duct Connections

IV. Venting

V. Coil Connections

VI. Electrical Connections

VII. Start-up and Adjustments

I

39379D36

4/15/72

I

i

L<-:

I.DO

’REMOVc- '

Figure 1—Model 48W-379A

In addition, the following section should be reviewed

by the equipment owner.

VIII. Maintenance

I. LOCATING THE UNIT

Extreme caution should be used when rigging and

moving the unit to prevent damage. The unit should
be kept upright during all rigging and moving
operations. To facilitate lifting and moving, place the
unit in an adequate sling made of rope or cable.

CAUTION: Be sure to protect the top and sides of the

unit from cable damage when rigging the unit to be
lifted.

Rooftop Installation

Level the unit on a base that is at least 6 inches above
the roof to provide drainage from beneath the unit.
Consult local codes for installation requirements. Be
sure that the roof will support the additional weight.

Ground Level Installation

If the unit is to be installed on the ground, it should
be placed on a level concrete slab with a minimum
thickness of 4 inches.