CRESTRON GREEN LIGHT™

Architectural Dimming

Load Wiring (Section B)

CAUTION: Bypass jumpers are provided on each output to allow testing and to protect the module during
installation. The jumper shorts the L, SW and DM terminals so that the load circuit is energized when the branch
breaker is on. Do not remove the bypass jumper until all feed and load wiring has been completed, and the circuits
have been tested for electrical faults.

NOTE: Use copper conductors only – rated 75

°C.

Wire Gauge and Torque Values

TERMINAL

CONNECTOR MAX WIRE RANGE

TORQUE

STRIP LENGTH

LOAD & DM OUTPUTS

26-10 AWG

5.31 lb-in (0.6 Nm) to
7.08 lb-in (0.8 Nm) max

3/8”
(9 mm)

DIM CONTROL
(GLX-DIMFLV8 only)

28-12 AWG

4.43 lb-in
(0.5 Nm)

5/16”
(8 mm)

GROUND BAR

14-10 AWG

35 lb-in
(4.0 Nm)

5/16”
(8 mm)

GROUND LUG

14-4 AWG

45-25 lb-in
(5.1-2.8 Nm)

3/4"
(19 mm)

1. Each output has a label with the number of the controlling circuit breaker printed on it. With the

corresponding circuit breaker turned off, connect the controlled circuit (LOAD) wires to the output per the
markings on the module as shown in the following diagrams. Terminals for load wiring accept one 10 – 14
AWG wire.

Load Wiring for GLX-DIM6, GLX-DIMFLV8, and GLX-HSW8 (Jumper Installed)

TO BRANCH BREAKER

(PREWIRED)

TO NEUTRAL BUS

(PREWIRED)

TO LOAD

JUMPER
(INSTALLED)

GLX-DIM6

GLX-HSW8 AND GLX-DIMFLV8

TO BRANCH BREAKER

(PREWIRED)

TO LOAD

TO NEUTRAL BUS

(PREWIRED)

TO LOAD

(3-WIRE BALLASTS
ONLY)

JUMPER
(INSTALLED)

Installation Guide – DOC. 6688A

CRESTRON GREEN LIGHT Architectural Dimming

7