Technologies inc, Sp-83, Please visit our website for other products – AZEL i-Link SERIES ZONE CONTROLS (CIRCULATOR PUMP SWITCHING RELAYS ) FOR HYDRONIC / RADIANT FLOOR HEATING SYSTEMS User Manual

Page 4: Set to master

Advertising
background image

Figure 4 Domestic Hot Water Priority with zone expansion by adding SP-83

Figure 5 24VAC High Limit & Gas Valve

TROUBLE SHOOTING

When 120VAC is supplied to

i-Link controllers, the green

indicator light should be on. When the thermostat calls for heat,
both the red indicator light and the circulator should be on.

!

If the green light is on and the circulator cannot be turned
on by the thermostat(red light is off)
, remove the thermostat
and put a piece of wire across the thermostat terminals (R/T
and W/T) to simulate thermostat calling for heat. If the
circulator can be turned on along with the red light, then check
the thermostat for functionality.

!

If both green light and red light are on and the circulator
cannot be turned on
, re-tighten the screws for the jumper on
terminal ZC and ZR in case of Cold Start Boiler Application and
try again.

!

If red light is on all the time, check the thermostat for

functionality. Remove the thermostat from the

i-Link controller

and put a piece of wire across R/T and W/T terminal to simulate
the thermostat calling for heat. If everything works properly,
then the thermostat is faulty.

If the green light is off, check the fuse and the presence of

120VAC power supply. If the fuse is fine and there is no power
output on 24VAC and COM terminals, the transformer needs
to be replaced.

Transformer models:
0511F : For SP-82 & SP-83
1011F: For SP-84, SP-85 & SP-86

P.O. Box 53138

10 Royal Orchard Blvd.

Thornhill, Ontario, Canada L3T 7R9

Ph: 905-223-5567 Fax: 905-223-3778

Email: [email protected]

www.azeltec.com

A

ZEL

TECHNOLOGIES INC.

Please visit our website for other products

ZC ZR

N L

120 Vac

120 VOLT CIRCULATORS

SYS PMP ZONE 1 ZONE 2 ZONE 3

N L N L N L N L

Zone 2

Circulator

Zone 1

Circulator

Zone 3

Circulator

120 VAC
(HOT)

(COM)

ON

ZONE 1 PRIORITY

OFF

MASTER SLAVE

ZONE EXPANSION

ZONE 1

T1 T1 T2 T2 T3 T3

1 2 3 4

R W R W R W

THERMOSTATS

TIMER

THERMOSTATS

X

SP-83

24VAC

TRANSFORMER

24V

GAS VALVE

OUTPUT

24

VAC

COM

X1

X1

X

ISOLATED

END SWITCH

HONEYWELL 4006A

120VAC

Set to Master

ON

ZONE 1 PRIORITY

OFF

24

VAC

ZC ZR

N L

120 Vac

120 VOLT CIRCULATORS

SYS PMP ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6

N L N L N L N L N L N L N L

Factory
Installed
Jumper

System

Circulator
(Optional)

Zone 2

Circulator

Zone 4

Circulator

Zone 6

Circulator

Zone 1

DHW

Circulator

Zone 3

Circulator

Zone 5

Circulator

OFF

Zone

2 3 4 5 6

X1

TIMER

ZONE 1 PRIORITY

OFF

TIMER

ZC ZR

N L

120 Vac

120 VOLT CIRCULATORS

SYS PMP ZONE 1 ZONE 2 ZONE 3

N L N L N L N L

Zone 7

Circulator

Zone 9

Circulator

Zone 8

Circulator

120 VAC
(HOT)

(COM)

120 VAC
(HOT)

(COM)

Note: The terminal block 1, 2, 3, 4 has extra large

hole which can take two wires at the same time

for easy expansion to the third units and more.

MASTER SLAVE

ZONE EXPANSION

OUTPUT

T1 T1 T2 T2 T3 T3 T4 T4 T5 T5 T6 T6

1 2 3 4

C

R W R W R W R W R W R W

THERMOSTATS

Boiler/
Burner
Control

T

T

THERMOSTATS

(eg. Azel Tech, D-135E)

AQUASTAT ON INDIRECT/

DOMESTIC HOT WATER

(DHW) HEATER

COM

R W

3 WIRE

THERMOSTAT

Honeywell

L8148

MANUAL

PRIORITY OVERRIDE

ON

X

X

X1

ISOLATED

END SWITCH

ZONE 1

TT on Boiler with

DHW TT Terminals

Boiler
Control

T

T

DHW

ON

MASTER SLAVE

Set to Slave

ZONE EXPANSION

ZONE 1

T1 T1 T2 T2 T3 T3

1 2 3 4

R W R W R W

THERMOSTATS

THERMOSTATS

X

OUTPUT

24

VAC

COM

X1

X1

X

ISOLATED

END SWITCH

Set to ON or Timer

Set to Master

Advertising