Nor-Cal SDC15 Controller User Manual

Quick reference guide, Pv input range table, List of alarm code

Advertising
background image

1

8

Alarm

Failure name

Cause

Corrective action

code

AL0 1

PV input failure

Sensor burnout, incorrect Check the wiring.

(Over-range)

wiring, incorrect PV input

Set the PV input type

type setting

again.

AL02

PV input failure

Sensor burnout, incorrect

(Under-range)

wiring, incorrect PV input
type setting

AL03

CJ failure

Terminal temperature is

Check the ambient

faulty (thermocouple).

temperature.

PV input failure

Sensor burnout, incorrect Check the wiring.

(RTD)

wiring

AL 1 1

CT input failure

A current exceeding the

• Use a CT with the

(Over-range)

upper limit of the display

correct number of turns

(CT input 1 or 2,

range was measured.

for the display range.

or both)

The number of CT turns

• Reset the number of CT

or the number of CT power

turns.

wire loops is incorrectly

• Reset the number of CT

set, or wiring is incorrect.

power wire loops.

• Check the wiring.

AL70

A/D conversion

A/D converter is faulty.

Replace the unit.

failure

AL95

Parameter failure

Power is shut-down while • Restart the unit.
the data is being set, or

• Set the data again (set

data is corrupted by noise. data for AL95/97 and

AL96

Adjustment data

Power is shut-down while

adjustment data for

failure

the data is being set, or

AL96/98.

data is corrupted by noise. • Replace the unit.

AL97

Parameter failure

Data is corrupted by

(RAM area)

noise.

AL98

Adjustment data

Data is corrupted by

failure (RAM area) noise.

AL99

ROM failure

ROM (memory) is faulty.

• Reset the unit.
• Replace the unit.

Quick Reference Guide

C01

Sensor

Range

Set value

type

1

K

-200 to +1200°C

2

K

0 to 1200°C

3

K

0 to 800°C

4

K

0 to 600°C

5

K

0 to 400°C

6

K

-200 to +400°C

9

J

0 to 800°C

10

J

0 to 600°C

11

J

-200 to +400°C

13

E

0 to 600°C

14

T

-200 to +400°C

15

R

0 to 1600°C

16

S

0 to 1600°C

17

B

0 to 1800°C

18

N

0 to 1300°C

19

PL II

0 to 1300°C

20

WRe5-26

0 to 1400°C

21

WRe5-26

0 to 2300°C

24

DIN U

-200 to +400°C

25

DIN L

-100 to +800°C

CP-SP-1213E

This guide offers a summary of key operations, parameter flowcharts, and settings, for
convenient reference at the operation site. This guide is made for repeated use. Dirt wipes
off easily and even notes written with an oil-based felt-tip pen can be removed with an
eraser. If more detailed information on the SDC15 is needed, refer to the user's manuals:
CP-SP-1147E for basic operation and CP-SP-1148E for installation and configuration.

The most convenient way to configure the SDC15 is with the Smart Loader Package
(model No. SLP-C35J50). Please contact Yamatake Corporation or a distributor for more

information.

[mode] key

[para] key

Lower display

Upper display

Loader connector
(bottom panel)

Mode indicators

[ ], [ ], and [ ] keys

Various indicators

Indicators during AT

PV input range table

C01

Sensor

Range

Set value

type

41

Pt100

-200 to +500°C

42

JPt100

-200 to +500°C

43

Pt100

-200 to +200°C

44

JPt100

-200 to +200°C

45

Pt100

-100 to +300°C

46

JPt100

-100 to +300°C

51

Pt100

-50.0 to +200.0°C

52

JPt100

-50.0 to +200.0°C

53

Pt100

-50.0 to +100.0°C

54

JPt100

-50.0 to +100.0°C

63

Pt100

0 to 200.0°C

64

JPt100

0 to 200.0°C

67

Pt100

0 to 500°C

68

JPt100

0 to 500°C

[Thermocouple]

[RTD]

[DC voltage/DC current]

: Initial value

*1: PL II thermocouple is a range, which has been added to the units manufactured

form July, 2003.

*2: The indicated low limit for a B thermocouple is 20°C. However, if ROM version 1

of the instrument information bank (I d02) is prior to 2.04, the value is
-180°C.

*3: Thermocouple, RTD, and DC voltage/DC current are according to PV No. type.

List of alarm code

Handling precautions

• If ROM version 1 of the instrument information bank (I d02) is prior to 2.04, CT

input failure (AL 1 1) is not displayed.

Event type

Event types other than the above:

: initial value

*: If the main setting is greater than the sub-setting, operations are performed with the main

setting and sub-setting automatically swapped.

Upper display

This display shows either the PV value or the display value and set value for
each displayed item. If an alarm is triggered, the normal display and alarm
code are displayed alternately. During auto tuning (AT), the rightmost decimal
point flashes twice repeatedly.

Lower display

This display shows either the SP/MV/CT or the display value and set value
for each displayed item. The rightmost decimal point lights up or flashes
to show RUN/READY mode or communications status, depending on the
setting.

Mode indicators

rdy:

Lights when READY (RUN mode if not lit)

man:

Lights when MANUAL (AUTO mode if not lit)

ev1, ev2, ev3: Lights when event relays are ON
ot1, ot2:

Lights when the control output is ON (always lit when the
current output is used)

[mode] key

• When this key is pressed and held for more than 1 second in the operation

display mode, any of the following operations from 0 to 7 which have been
set previously can be executed:

0 : Mode key does not operate (Initial value)
1 : AUTO/MANUAL mode selection
2 : RUN/READY mode selection
3 : AT (Auto Tuning) start/stop selection
4 : LSP (Local SP) group selection
5 : Release all DO (Digital Output) latches
6 : Mode key does not operate
7 : ON/OFF selection of communication DI

• When pressing the [mode] key in the setup display mode, the display is

changed to the operation display

[para] key

• This key is used to change the display item.
• When this key is kept pressed for 2 sec. or longer in the operation display

mode, the display is then changed to the setup display

[<], [ ], [ ] keys

Theses keys are used to increase or decrease the numeric value, or to shift
the digit.

Loader connector

The Smart Loader connector is on the bottom of the SDC15.

C01

Sensor

Range

Set value

type

84

0 to 1V

Scaling range is

86

1 to 5V

-1999 to +9999.

87

0 to 5V

88

0 to 10V

89

0 to 20mA

90

4 to 20mA

Operation type

Set value

SP high limit

10

SP low limit

11

SP high/low limit

12

MV high limit

13

MV low limit

14

MV high/low limit

15

Operation type

Set value

Loop diagnosis 1

20

Loop diagnosis 2

21

Loop diagnosis 3

22

READY (status)

24

MANUAL (status)

25

Operation type

Set value

During AT (status)

27

During SP ramp

28

Control action (status)

29

ST setting standby (status)

30

Timer (status)

32

Specifications are subject to change without notice.

Advanced Automation Company

1-12-2 Kawana, Fujisawa
Kanagawa 251-8522 Japan

URL: http://www.azbil.com

Printed on recycled paper.

(07)

Printed in Japan.

1st Edition: Issued in Mar. 2007 (W)

Operation

Set

Direct action

Reverse action

type

value

No event

0

Always OFF

Always OFF

PV high

1

limit

PV low

2

limit

PV high/

3

low limit

Deviation

4

high limit

Deviation

5

low limit

Deviation

6

high/low

limit

Deviation

7

high limit

(Final SP

reference)
Deviation

8

low limit

(Final SP

reference)
Deviation

9

high/low
limit
(Final SP
reference)
Heater 1

16

burnout/
Over-
current

Heater 1

17

short-
circuit

Heater 2

18

burnout/
Over-
current

Heater 2

19

short-
circuit

Alarm 23

ON if alarm occurs (alarm code AL01 to 99).

OFF if alarm occurs (alarm code AL01 to 99).

(status)

OFF in other cases.

ON in other cases.

● shows that the ON/OFF is changed at this value.
O shows that the ON/OFF is changed at a point that

"1U" is added to this value.

● shows that the ON/OFF is changed at this value.
O shows that the ON/OFF is changed at a point that

"1U" is added to this value.

Main setting

PV

ON

HYS

Main setting *

Sub-setting *

PV

ON

HYS

ON

HYS

ON

HYS

SP + Main setting PV

ON

HYS

SP + Main setting PV

SP + Main setting

PV

ON

HYS

SP + Main setting

PV

ON

HYS

Main setting Sub-setting

PV

SP

ON

HYS

ON

HYS

ON

HYS

HYS

Main setting

Sub-setting

SP

PV

ON

HYS

SP + Main setting PV

ON

HYS

SP + Main setting PV

SP + Main setting

PV

ON

HYS

SP + Main setting

PV

ON

HYS

Main setting Sub-setting

PV

SP

ON

HYS

ON

HYS

ON

HYS

HYS

Main setting

Sub-setting

SP

PV

Main setting *

Sub-setting *

CT1 at output ON

ON

HYS

ON

HYS

OFF before measuring the CT1 current value

CT1 at output ON

ON

HYS

HYS

Main setting *

Sub-setting *

OFF before measuring CT1 current value

ON

HYS

Main setting

PV

ON

HYS

Main setting

PV

Main setitng *

Sub-setting *

CT2 at output ON

ON

HYS

ON

HYS

OFF before measuring CT2 current value

CT2 at output ON

ON

HYS

HYS

Main setting *

Sub-setting *

OFF before measuirng CT2 current value

ON

HYS

Main setting

CT2 at output OFF

OFF before measuring CT2 current value

ON

HYS

Main setting

CT2 at output OFF

OFF before measuring CT2 current value

ON

HYS

Main setting

CT1 at output OFF

OFF before measuring CT1 current value

ON

HYS

Main setting

CT1 at output OFF

OFF before measuring CT1 current value

Main setting

PV

ON

HYS

<

<

Input failure

Unit failure

Advertising